Kabelarea för 125 Ampere vid 300 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 125 A över 300 m vid 400V.

Copper Cable (≤3% Drop)120 mm²Drop: 11.58V (2.9%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 9.55V (2.39%)
Voltage at Load388.4 VLine Loss: 2507.8 W
Max Power & Breaker86.6 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A926.65 V (231.66%)0.0 V1528.53 V (382.13%)200625.0 WDrop High
2.5 mm²24 A18 A555.99 V (139.0%)0.0 V917.12 V (229.28%)120375.0 WDrop High
4 mm²32 A25 A347.49 V (86.87%)52.5 V573.2 V (143.3%)75234.4 WDrop High
6 mm²41 A32 A231.66 V (57.92%)168.3 V382.13 V (95.53%)50156.2 WDrop High
10 mm²57 A44 A139.0 V (34.75%)261.0 V229.28 V (57.32%)30093.8 WDrop High
16 mm²76 A59 A86.87 V (21.72%)313.1 V143.3 V (35.83%)18808.6 WDrop High
25 mm²101 A78 A55.6 V (13.9%)344.4 V91.71 V (22.93%)12037.5 WDrop High
35 mm²125 A97 A39.71 V (9.93%)360.3 V65.51 V (16.38%)8598.2 WDrop High
50 mm²151 A118 A27.8 V (6.95%)372.2 V45.86 V (11.46%)6018.7 WDrop High
70 mm²192 A150 A19.86 V (4.96%)380.1 V32.75 V (8.19%)4299.1 W~ ≤5%
95 mm²232 A181 A14.63 V (3.66%)385.4 V24.13 V (6.03%)3167.8 W~ ≤5%
120 mm²269 A210 A11.58 V (2.9%)388.4 V19.11 V (4.78%)2507.8 W✓ OK (≤3%)
150 mm²309 A241 A9.27 V (2.32%)390.7 V15.29 V (3.82%)2006.2 W✓ OK (≤3%)
185 mm²353 A275 A7.51 V (1.88%)392.5 V12.39 V (3.1%)1626.7 W✓ OK (≤3%)
240 mm²415 A324 A5.79 V (1.45%)394.2 V9.55 V (2.39%)1253.9 W✓ OK (≤3%)
300 mm²477 A372 A4.63 V (1.16%)395.4 V7.64 V (1.91%)1003.1 W✓ OK (≤3%)
400 mm²570 A445 A3.47 V (0.87%)396.5 V5.73 V (1.43%)752.3 W✓ OK (≤3%)

FAQ — Kabelarea för 125 Ampere vid 300 Meter (400V)

Vilken kabelarea krävs för 125A vid 300 meter (400V)?

För 125 Ampere över 300 meter vid 400V rekommenderas 120 mm² kopparkabel för att hålla spänningsfallet under 3% (11.58V / 2.9%).

Hur stor effekt motsvarar 125A vid 400V?

Det motsvarar 86.6 kW med en rekommenderad säkring på 125A.