⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 160 Ampere vid 300 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 160 A över 300 m vid 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 11.86V (2.97%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 9.78V (2.45%)
Voltage at Load388.1 VLine Loss: 3287.0 W
Max Power & Breaker110.85 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1186.11 V (296.53%)0.0 V1956.52 V (489.13%)328704.0 WDrop High
2.5 mm²24 A18 A711.67 V (177.92%)0.0 V1173.91 V (293.48%)197222.4 WDrop High
4 mm²32 A25 A444.79 V (111.2%)0.0 V733.7 V (183.42%)123264.0 WDrop High
6 mm²41 A32 A296.53 V (74.13%)103.5 V489.13 V (122.28%)82176.0 WDrop High
10 mm²57 A44 A177.92 V (44.48%)222.1 V293.48 V (73.37%)49305.6 WDrop High
16 mm²76 A59 A111.2 V (27.8%)288.8 V183.42 V (45.86%)30816.0 WDrop High
25 mm²101 A78 A71.17 V (17.79%)328.8 V117.39 V (29.35%)19722.2 WDrop High
35 mm²125 A97 A50.83 V (12.71%)349.2 V83.85 V (20.96%)14087.3 WDrop High
50 mm²151 A118 A35.58 V (8.9%)364.4 V58.7 V (14.67%)9861.1 WDrop High
70 mm²192 A150 A25.42 V (6.35%)374.6 V41.93 V (10.48%)7043.7 WDrop High
95 mm²232 A181 A18.73 V (4.68%)381.3 V30.89 V (7.72%)5190.1 W~ ≤5%
120 mm²269 A210 A14.83 V (3.71%)385.2 V24.46 V (6.11%)4108.8 W~ ≤5%
150 mm²309 A241 A11.86 V (2.97%)388.1 V19.57 V (4.89%)3287.0 W✓ OK (≤3%)
185 mm²353 A275 A9.62 V (2.4%)390.4 V15.86 V (3.97%)2665.2 W✓ OK (≤3%)
240 mm²415 A324 A7.41 V (1.85%)392.6 V12.23 V (3.06%)2054.4 W✓ OK (≤3%)
300 mm²477 A372 A5.93 V (1.48%)394.1 V9.78 V (2.45%)1643.5 W✓ OK (≤3%)
400 mm²570 A445 A4.45 V (1.11%)395.6 V7.34 V (1.83%)1232.6 W✓ OK (≤3%)

FAQ — Kabelarea för 160 Ampere vid 300 Meter (400V)

Vilken kabelarea krävs för 160A vid 300 meter (400V)?

För 160 Ampere över 300 meter vid 400V rekommenderas 150 mm² kopparkabel för att hålla spänningsfallet under 3% (11.86V / 2.97%).

Hur stor effekt motsvarar 160A vid 400V?

Det motsvarar 110.85 kW med en rekommenderad säkring på 160A.