Kabelarea för 600 Ampere vid 500 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 600 A över 500 m vid 400V.

Copper Cable (≤3% Drop)3× 400 mm²Drop: 9.27V (2.32%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 45.86V (11.46%)
Voltage at Load390.7 VLine Loss: 9630.0 W
Max Power & Breaker415.69 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7413.18 V (1853.29%)0.0 V12228.28 V (3057.07%)7704000.0 WDrop High
2.5 mm²24 A18 A4447.91 V (1111.98%)0.0 V7336.97 V (1834.24%)4622400.0 WDrop High
4 mm²32 A25 A2779.94 V (694.99%)0.0 V4585.6 V (1146.4%)2889000.0 WDrop High
6 mm²41 A32 A1853.29 V (463.32%)0.0 V3057.07 V (764.27%)1926000.0 WDrop High
10 mm²57 A44 A1111.98 V (277.99%)0.0 V1834.24 V (458.56%)1155600.0 WDrop High
16 mm²76 A59 A694.99 V (173.75%)0.0 V1146.4 V (286.6%)722250.0 WDrop High
25 mm²101 A78 A444.79 V (111.2%)0.0 V733.7 V (183.42%)462240.0 WDrop High
35 mm²125 A97 A317.71 V (79.43%)82.3 V524.07 V (131.02%)330171.4 WDrop High
50 mm²151 A118 A222.4 V (55.6%)177.6 V366.85 V (91.71%)231120.0 WDrop High
70 mm²192 A150 A158.85 V (39.71%)241.1 V262.03 V (65.51%)165085.7 WDrop High
95 mm²232 A181 A117.05 V (29.26%)282.9 V193.08 V (48.27%)121642.1 WDrop High
120 mm²269 A210 A92.66 V (23.17%)307.3 V152.85 V (38.21%)96300.0 WDrop High
150 mm²309 A241 A74.13 V (18.53%)325.9 V122.28 V (30.57%)77040.0 WDrop High
185 mm²353 A275 A60.11 V (15.03%)339.9 V99.15 V (24.79%)62464.9 WDrop High
240 mm²415 A324 A46.33 V (11.58%)353.7 V76.43 V (19.11%)48150.0 WDrop High
300 mm²477 A372 A37.07 V (9.27%)362.9 V61.14 V (15.29%)38520.0 WDrop High
400 mm²570 A445 A27.8 V (6.95%)372.2 V45.86 V (11.46%)28890.0 WDrop High

FAQ — Kabelarea för 600 Ampere vid 500 Meter (400V)

Vilken kabelarea krävs för 600A vid 500 meter (400V)?

För 600 Ampere över 500 meter vid 400V rekommenderas 3× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (9.27V / 2.32%).

Hur stor effekt motsvarar 600A vid 400V?

Det motsvarar 415.69 kW med en rekommenderad säkring på 600A.