Kabelarea för 63 Ampere vid 10 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 10 m vid 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 1.46V (0.36%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 1.54V (0.39%)
Voltage at Load398.5 VLine Loss: 159.3 W
Max Power & Breaker43.65 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A15.57 V (3.89%)384.4 V25.68 V (6.42%)1698.7 WDrop High
2.5 mm²24 A18 A9.34 V (2.34%)390.7 V15.41 V (3.85%)1019.2 WDrop High
4 mm²32 A25 A5.84 V (1.46%)394.2 V9.63 V (2.41%)637.0 WDrop High
6 mm²41 A32 A3.89 V (0.97%)396.1 V6.42 V (1.6%)424.7 WDrop High
10 mm²57 A44 A2.34 V (0.58%)397.7 V3.85 V (0.96%)254.8 WDrop High
16 mm²76 A59 A1.46 V (0.36%)398.5 V2.41 V (0.6%)159.3 W✓ OK (≤3%)
25 mm²101 A78 A0.93 V (0.23%)399.1 V1.54 V (0.39%)101.9 W✓ OK (≤3%)
35 mm²125 A97 A0.67 V (0.17%)399.3 V1.1 V (0.28%)72.8 W✓ OK (≤3%)
50 mm²151 A118 A0.47 V (0.12%)399.5 V0.77 V (0.19%)51.0 W✓ OK (≤3%)
70 mm²192 A150 A0.33 V (0.08%)399.7 V0.55 V (0.14%)36.4 W✓ OK (≤3%)
95 mm²232 A181 A0.25 V (0.06%)399.8 V0.41 V (0.1%)26.8 W✓ OK (≤3%)
120 mm²269 A210 A0.19 V (0.05%)399.8 V0.32 V (0.08%)21.2 W✓ OK (≤3%)
150 mm²309 A241 A0.16 V (0.04%)399.8 V0.26 V (0.06%)17.0 W✓ OK (≤3%)
185 mm²353 A275 A0.13 V (0.03%)399.9 V0.21 V (0.05%)13.8 W✓ OK (≤3%)
240 mm²415 A324 A0.1 V (0.02%)399.9 V0.16 V (0.04%)10.6 W✓ OK (≤3%)
300 mm²477 A372 A0.08 V (0.02%)399.9 V0.13 V (0.03%)8.5 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.01%)399.9 V0.1 V (0.02%)6.4 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 10 Meter (400V)

Vilken kabelarea krävs för 63A vid 10 meter (400V)?

För 63 Ampere över 10 meter vid 400V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (1.46V / 0.36%).

Hur stor effekt motsvarar 63A vid 400V?

Det motsvarar 43.65 kW med en rekommenderad säkring på 63A.