Kabelarea för 63 Ampere vid 60 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 60 m vid 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 8.76V (2.19%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 9.24V (2.31%)
Voltage at Load391.2 VLine Loss: 955.5 W
Max Power & Breaker43.65 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A93.41 V (23.35%)306.6 V154.08 V (38.52%)10192.4 WDrop High
2.5 mm²24 A18 A56.04 V (14.01%)344.0 V92.45 V (23.11%)6115.4 WDrop High
4 mm²32 A25 A35.03 V (8.76%)365.0 V57.78 V (14.44%)3822.1 WDrop High
6 mm²41 A32 A23.35 V (5.84%)376.6 V38.52 V (9.63%)2548.1 WDrop High
10 mm²57 A44 A14.01 V (3.5%)386.0 V23.11 V (5.78%)1528.9 WDrop High
16 mm²76 A59 A8.76 V (2.19%)391.2 V14.44 V (3.61%)955.5 W✓ OK (≤3%)
25 mm²101 A78 A5.6 V (1.4%)394.4 V9.24 V (2.31%)611.5 W✓ OK (≤3%)
35 mm²125 A97 A4.0 V (1.0%)396.0 V6.6 V (1.65%)436.8 W✓ OK (≤3%)
50 mm²151 A118 A2.8 V (0.7%)397.2 V4.62 V (1.16%)305.8 W✓ OK (≤3%)
70 mm²192 A150 A2.0 V (0.5%)398.0 V3.3 V (0.83%)218.4 W✓ OK (≤3%)
95 mm²232 A181 A1.47 V (0.37%)398.5 V2.43 V (0.61%)160.9 W✓ OK (≤3%)
120 mm²269 A210 A1.17 V (0.29%)398.8 V1.93 V (0.48%)127.4 W✓ OK (≤3%)
150 mm²309 A241 A0.93 V (0.23%)399.1 V1.54 V (0.39%)101.9 W✓ OK (≤3%)
185 mm²353 A275 A0.76 V (0.19%)399.2 V1.25 V (0.31%)82.6 W✓ OK (≤3%)
240 mm²415 A324 A0.58 V (0.15%)399.4 V0.96 V (0.24%)63.7 W✓ OK (≤3%)
300 mm²477 A372 A0.47 V (0.12%)399.5 V0.77 V (0.19%)51.0 W✓ OK (≤3%)
400 mm²570 A445 A0.35 V (0.09%)399.6 V0.58 V (0.14%)38.2 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 60 Meter (400V)

Vilken kabelarea krävs för 63A vid 60 meter (400V)?

För 63 Ampere över 60 meter vid 400V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (8.76V / 2.19%).

Hur stor effekt motsvarar 63A vid 400V?

Det motsvarar 43.65 kW med en rekommenderad säkring på 63A.