Kabelarea för 70 Ampere vid 120 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 70 A över 120 m vid 230V.

Copper Cable (≤3% Drop)70 mm²Drop: 5.14V (2.23%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 6.24V (2.71%)
Voltage at Load224.9 VLine Loss: 359.5 W
Max Power & Breaker16.1 kW70A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 70A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A239.68 V (104.21%)0.0 V395.36 V (171.9%)16777.6 WDrop High
2.5 mm²24 A18 A143.81 V (62.53%)86.2 V237.22 V (103.14%)10066.6 WDrop High
4 mm²32 A25 A89.88 V (39.08%)140.1 V148.26 V (64.46%)6291.6 WDrop High
6 mm²41 A32 A59.92 V (26.05%)170.1 V98.84 V (42.97%)4194.4 WDrop High
10 mm²57 A44 A35.95 V (15.63%)194.0 V59.3 V (25.78%)2516.6 WDrop High
16 mm²76 A59 A22.47 V (9.77%)207.5 V37.06 V (16.12%)1572.9 WDrop High
25 mm²101 A78 A14.38 V (6.25%)215.6 V23.72 V (10.31%)1006.7 WDrop High
35 mm²125 A97 A10.27 V (4.47%)219.7 V16.94 V (7.37%)719.0 W~ ≤5%
50 mm²151 A118 A7.19 V (3.13%)222.8 V11.86 V (5.16%)503.3 W~ ≤5%
70 mm²192 A150 A5.14 V (2.23%)224.9 V8.47 V (3.68%)359.5 W✓ OK (≤3%)
95 mm²232 A181 A3.78 V (1.65%)226.2 V6.24 V (2.71%)264.9 W✓ OK (≤3%)
120 mm²269 A210 A3.0 V (1.3%)227.0 V4.94 V (2.15%)209.7 W✓ OK (≤3%)
150 mm²309 A241 A2.4 V (1.04%)227.6 V3.95 V (1.72%)167.8 W✓ OK (≤3%)
185 mm²353 A275 A1.94 V (0.84%)228.1 V3.21 V (1.39%)136.0 W✓ OK (≤3%)
240 mm²415 A324 A1.5 V (0.65%)228.5 V2.47 V (1.07%)104.9 W✓ OK (≤3%)
300 mm²477 A372 A1.2 V (0.52%)228.8 V1.98 V (0.86%)83.9 W✓ OK (≤3%)
400 mm²570 A445 A0.9 V (0.39%)229.1 V1.48 V (0.64%)62.9 W✓ OK (≤3%)

FAQ — Kabelarea för 70 Ampere vid 120 Meter (230V)

Vilken kabelarea krävs för 70A vid 120 meter (230V)?

För 70 Ampere över 120 meter vid 230V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (5.14V / 2.23%).

Hur stor effekt motsvarar 70A vid 230V?

Det motsvarar 16.1 kW med en rekommenderad säkring på 70A.