Kabelarea för 16 Ampere vid 120 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 16 A över 120 m vid 230V.

Copper Cable (≤3% Drop)16 mm²Drop: 5.14V (2.23%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 5.42V (2.36%)
Voltage at Load224.9 VLine Loss: 82.2 W
Max Power & Breaker3.68 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A54.78 V (23.82%)175.2 V90.37 V (39.29%)876.5 WDrop High
2.5 mm²24 A18 A32.87 V (14.29%)197.1 V54.22 V (23.57%)525.9 WDrop High
4 mm²32 A25 A20.54 V (8.93%)209.5 V33.89 V (14.73%)328.7 WDrop High
6 mm²41 A32 A13.7 V (5.95%)216.3 V22.59 V (9.82%)219.1 WDrop High
10 mm²57 A44 A8.22 V (3.57%)221.8 V13.56 V (5.89%)131.5 W~ ≤5%
16 mm²76 A59 A5.14 V (2.23%)224.9 V8.47 V (3.68%)82.2 W✓ OK (≤3%)
25 mm²101 A78 A3.29 V (1.43%)226.7 V5.42 V (2.36%)52.6 W✓ OK (≤3%)
35 mm²125 A97 A2.35 V (1.02%)227.7 V3.87 V (1.68%)37.6 W✓ OK (≤3%)
50 mm²151 A118 A1.64 V (0.71%)228.4 V2.71 V (1.18%)26.3 W✓ OK (≤3%)
70 mm²192 A150 A1.17 V (0.51%)228.8 V1.94 V (0.84%)18.8 W✓ OK (≤3%)
95 mm²232 A181 A0.87 V (0.38%)229.1 V1.43 V (0.62%)13.8 W✓ OK (≤3%)
120 mm²269 A210 A0.68 V (0.3%)229.3 V1.13 V (0.49%)11.0 W✓ OK (≤3%)
150 mm²309 A241 A0.55 V (0.24%)229.5 V0.9 V (0.39%)8.8 W✓ OK (≤3%)
185 mm²353 A275 A0.44 V (0.19%)229.6 V0.73 V (0.32%)7.1 W✓ OK (≤3%)
240 mm²415 A324 A0.34 V (0.15%)229.7 V0.56 V (0.25%)5.5 W✓ OK (≤3%)
300 mm²477 A372 A0.27 V (0.12%)229.7 V0.45 V (0.2%)4.4 W✓ OK (≤3%)
400 mm²570 A445 A0.21 V (0.09%)229.8 V0.34 V (0.15%)3.3 W✓ OK (≤3%)

FAQ — Kabelarea för 16 Ampere vid 120 Meter (230V)

Vilken kabelarea krävs för 16A vid 120 meter (230V)?

För 16 Ampere över 120 meter vid 230V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (5.14V / 2.23%).

Hur stor effekt motsvarar 16A vid 230V?

Det motsvarar 3.68 kW med en rekommenderad säkring på 16A.