Kabelarea för 80 Ampere vid 120 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 80 A över 120 m vid 230V.

Copper Cable (≤3% Drop)70 mm²Drop: 5.87V (2.55%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 5.65V (2.46%)
Voltage at Load224.1 VLine Loss: 469.6 W
Max Power & Breaker18.4 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A273.92 V (119.1%)0.0 V451.84 V (196.45%)21913.6 WDrop High
2.5 mm²24 A18 A164.35 V (71.46%)65.6 V271.1 V (117.87%)13148.2 WDrop High
4 mm²32 A25 A102.72 V (44.66%)127.3 V169.44 V (73.67%)8217.6 WDrop High
6 mm²41 A32 A68.48 V (29.77%)161.5 V112.96 V (49.11%)5478.4 WDrop High
10 mm²57 A44 A41.09 V (17.86%)188.9 V67.78 V (29.47%)3287.0 WDrop High
16 mm²76 A59 A25.68 V (11.17%)204.3 V42.36 V (18.42%)2054.4 WDrop High
25 mm²101 A78 A16.44 V (7.15%)213.6 V27.11 V (11.79%)1314.8 WDrop High
35 mm²125 A97 A11.74 V (5.1%)218.3 V19.36 V (8.42%)939.2 WDrop High
50 mm²151 A118 A8.22 V (3.57%)221.8 V13.56 V (5.89%)657.4 W~ ≤5%
70 mm²192 A150 A5.87 V (2.55%)224.1 V9.68 V (4.21%)469.6 W✓ OK (≤3%)
95 mm²232 A181 A4.33 V (1.88%)225.7 V7.13 V (3.1%)346.0 W✓ OK (≤3%)
120 mm²269 A210 A3.42 V (1.49%)226.6 V5.65 V (2.46%)273.9 W✓ OK (≤3%)
150 mm²309 A241 A2.74 V (1.19%)227.3 V4.52 V (1.96%)219.1 W✓ OK (≤3%)
185 mm²353 A275 A2.22 V (0.97%)227.8 V3.66 V (1.59%)177.7 W✓ OK (≤3%)
240 mm²415 A324 A1.71 V (0.74%)228.3 V2.82 V (1.23%)137.0 W✓ OK (≤3%)
300 mm²477 A372 A1.37 V (0.6%)228.6 V2.26 V (0.98%)109.6 W✓ OK (≤3%)
400 mm²570 A445 A1.03 V (0.45%)229.0 V1.69 V (0.74%)82.2 W✓ OK (≤3%)

FAQ — Kabelarea för 80 Ampere vid 120 Meter (230V)

Vilken kabelarea krävs för 80A vid 120 meter (230V)?

För 80 Ampere över 120 meter vid 230V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (5.87V / 2.55%).

Hur stor effekt motsvarar 80A vid 230V?

Det motsvarar 18.4 kW med en rekommenderad säkring på 80A.