⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 10 Ampere vid 120 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 10 A över 120 m vid 230V.

Copper Cable (≤3% Drop)10 mm²Drop: 5.14V (2.23%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 5.29V (2.3%)
Voltage at Load224.9 VLine Loss: 51.4 W
Max Power & Breaker2.3 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A34.24 V (14.89%)195.8 V56.48 V (24.56%)342.4 WDrop High
2.5 mm²24 A18 A20.54 V (8.93%)209.5 V33.89 V (14.73%)205.4 WDrop High
4 mm²32 A25 A12.84 V (5.58%)217.2 V21.18 V (9.21%)128.4 WDrop High
6 mm²41 A32 A8.56 V (3.72%)221.4 V14.12 V (6.14%)85.6 W~ ≤5%
10 mm²57 A44 A5.14 V (2.23%)224.9 V8.47 V (3.68%)51.4 W✓ OK (≤3%)
16 mm²76 A59 A3.21 V (1.4%)226.8 V5.29 V (2.3%)32.1 W✓ OK (≤3%)
25 mm²101 A78 A2.05 V (0.89%)227.9 V3.39 V (1.47%)20.5 W✓ OK (≤3%)
35 mm²125 A97 A1.47 V (0.64%)228.5 V2.42 V (1.05%)14.7 W✓ OK (≤3%)
50 mm²151 A118 A1.03 V (0.45%)229.0 V1.69 V (0.74%)10.3 W✓ OK (≤3%)
70 mm²192 A150 A0.73 V (0.32%)229.3 V1.21 V (0.53%)7.3 W✓ OK (≤3%)
95 mm²232 A181 A0.54 V (0.24%)229.5 V0.89 V (0.39%)5.4 W✓ OK (≤3%)
120 mm²269 A210 A0.43 V (0.19%)229.6 V0.71 V (0.31%)4.3 W✓ OK (≤3%)
150 mm²309 A241 A0.34 V (0.15%)229.7 V0.56 V (0.25%)3.4 W✓ OK (≤3%)
185 mm²353 A275 A0.28 V (0.12%)229.7 V0.46 V (0.2%)2.8 W✓ OK (≤3%)
240 mm²415 A324 A0.21 V (0.09%)229.8 V0.35 V (0.15%)2.1 W✓ OK (≤3%)
300 mm²477 A372 A0.17 V (0.07%)229.8 V0.28 V (0.12%)1.7 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.06%)229.9 V0.21 V (0.09%)1.3 W✓ OK (≤3%)

FAQ — Kabelarea för 10 Ampere vid 120 Meter (230V)

Vilken kabelarea krävs för 10A vid 120 meter (230V)?

För 10 Ampere över 120 meter vid 230V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (5.14V / 2.23%).

Hur stor effekt motsvarar 10A vid 230V?

Det motsvarar 2.3 kW med en rekommenderad säkring på 10A.