Kabelarea för 70 Ampere vid 150 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 70 A över 150 m vid 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 9.17V (2.29%)
Voltage at Load388.9 VLine Loss: 1348.2 W
Max Power & Breaker48.5 kW70A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 70A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A259.46 V (64.87%)140.5 V427.99 V (107.0%)31458.0 WDrop High
2.5 mm²24 A18 A155.68 V (38.92%)244.3 V256.79 V (64.2%)18874.8 WDrop High
4 mm²32 A25 A97.3 V (24.32%)302.7 V160.5 V (40.12%)11796.8 WDrop High
6 mm²41 A32 A64.87 V (16.22%)335.1 V107.0 V (26.75%)7864.5 WDrop High
10 mm²57 A44 A38.92 V (9.73%)361.1 V64.2 V (16.05%)4718.7 WDrop High
16 mm²76 A59 A24.32 V (6.08%)375.7 V40.12 V (10.03%)2949.2 WDrop High
25 mm²101 A78 A15.57 V (3.89%)384.4 V25.68 V (6.42%)1887.5 W~ ≤5%
35 mm²125 A97 A11.12 V (2.78%)388.9 V18.34 V (4.59%)1348.2 W✓ OK (≤3%)
50 mm²151 A118 A7.78 V (1.95%)392.2 V12.84 V (3.21%)943.7 W✓ OK (≤3%)
70 mm²192 A150 A5.56 V (1.39%)394.4 V9.17 V (2.29%)674.1 W✓ OK (≤3%)
95 mm²232 A181 A4.1 V (1.02%)395.9 V6.76 V (1.69%)496.7 W✓ OK (≤3%)
120 mm²269 A210 A3.24 V (0.81%)396.8 V5.35 V (1.34%)393.2 W✓ OK (≤3%)
150 mm²309 A241 A2.59 V (0.65%)397.4 V4.28 V (1.07%)314.6 W✓ OK (≤3%)
185 mm²353 A275 A2.1 V (0.53%)397.9 V3.47 V (0.87%)255.1 W✓ OK (≤3%)
240 mm²415 A324 A1.62 V (0.41%)398.4 V2.67 V (0.67%)196.6 W✓ OK (≤3%)
300 mm²477 A372 A1.3 V (0.32%)398.7 V2.14 V (0.53%)157.3 W✓ OK (≤3%)
400 mm²570 A445 A0.97 V (0.24%)399.0 V1.6 V (0.4%)118.0 W✓ OK (≤3%)

FAQ — Kabelarea för 70 Ampere vid 150 Meter (400V)

Vilken kabelarea krävs för 70A vid 150 meter (400V)?

För 70 Ampere över 150 meter vid 400V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (11.12V / 2.78%).

Hur stor effekt motsvarar 70A vid 400V?

Det motsvarar 48.5 kW med en rekommenderad säkring på 70A.