Kabelarea för 700 Ampere vid 40 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 700 A över 40 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.29V (0.33%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.28V (1.07%)
Voltage at Load398.7 VLine Loss: 1572.9 W
Max Power & Breaker484.97 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A691.9 V (172.97%)0.0 V1141.31 V (285.33%)838880.0 WDrop High
2.5 mm²24 A18 A415.14 V (103.78%)0.0 V684.78 V (171.2%)503328.0 WDrop High
4 mm²32 A25 A259.46 V (64.87%)140.5 V427.99 V (107.0%)314580.0 WDrop High
6 mm²41 A32 A172.97 V (43.24%)227.0 V285.33 V (71.33%)209720.0 WDrop High
10 mm²57 A44 A103.78 V (25.95%)296.2 V171.2 V (42.8%)125832.0 WDrop High
16 mm²76 A59 A64.87 V (16.22%)335.1 V107.0 V (26.75%)78645.0 WDrop High
25 mm²101 A78 A41.51 V (10.38%)358.5 V68.48 V (17.12%)50332.8 WDrop High
35 mm²125 A97 A29.65 V (7.41%)370.3 V48.91 V (12.23%)35952.0 WDrop High
50 mm²151 A118 A20.76 V (5.19%)379.2 V34.24 V (8.56%)25166.4 WDrop High
70 mm²192 A150 A14.83 V (3.71%)385.2 V24.46 V (6.11%)17976.0 WDrop High
95 mm²232 A181 A10.92 V (2.73%)389.1 V18.02 V (4.51%)13245.5 WDrop High
120 mm²269 A210 A8.65 V (2.16%)391.4 V14.27 V (3.57%)10486.0 WDrop High
150 mm²309 A241 A6.92 V (1.73%)393.1 V11.41 V (2.85%)8388.8 WDrop High
185 mm²353 A275 A5.61 V (1.4%)394.4 V9.25 V (2.31%)6801.7 WDrop High
240 mm²415 A324 A4.32 V (1.08%)395.7 V7.13 V (1.78%)5243.0 WDrop High
300 mm²477 A372 A3.46 V (0.86%)396.5 V5.71 V (1.43%)4194.4 WDrop High
400 mm²570 A445 A2.59 V (0.65%)397.4 V4.28 V (1.07%)3145.8 WDrop High

FAQ — Kabelarea för 700 Ampere vid 40 Meter (400V)

Vilken kabelarea krävs för 700A vid 40 meter (400V)?

För 700 Ampere över 40 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (1.29V / 0.33%).

Hur stor effekt motsvarar 700A vid 400V?

Det motsvarar 484.97 kW med en rekommenderad säkring på 700A.