Kabelarea för 700 Ampere vid 70 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 700 A över 70 m vid 400V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.27V (0.57%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.49V (1.87%)
Voltage at Load397.7 VLine Loss: 2752.6 W
Max Power & Breaker484.97 kW700A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 70m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1210.82 V (302.7%) | 0.0 V | 1997.29 V (499.32%) | 1468040.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 726.49 V (181.62%) | 0.0 V | 1198.37 V (299.59%) | 880824.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 454.06 V (113.51%) | 0.0 V | 748.98 V (187.25%) | 550515.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 302.7 V (75.68%) | 97.3 V | 499.32 V (124.83%) | 367010.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 181.62 V (45.41%) | 218.4 V | 299.59 V (74.9%) | 220206.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 113.51 V (28.38%) | 286.5 V | 187.25 V (46.81%) | 137628.8 W | Drop High |
| 25 mm² | 101 A | 78 A | 72.65 V (18.16%) | 327.4 V | 119.84 V (29.96%) | 88082.4 W | Drop High |
| 35 mm² | 125 A | 97 A | 51.89 V (12.97%) | 348.1 V | 85.6 V (21.4%) | 62916.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 36.32 V (9.08%) | 363.7 V | 59.92 V (14.98%) | 44041.2 W | Drop High |
| 70 mm² | 192 A | 150 A | 25.95 V (6.49%) | 374.1 V | 42.8 V (10.7%) | 31458.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 19.12 V (4.78%) | 380.9 V | 31.54 V (7.88%) | 23179.6 W | Drop High |
| 120 mm² | 269 A | 210 A | 15.14 V (3.78%) | 384.9 V | 24.97 V (6.24%) | 18350.5 W | Drop High |
| 150 mm² | 309 A | 241 A | 12.11 V (3.03%) | 387.9 V | 19.97 V (4.99%) | 14680.4 W | Drop High |
| 185 mm² | 353 A | 275 A | 9.82 V (2.45%) | 390.2 V | 16.19 V (4.05%) | 11903.0 W | Drop High |
| 240 mm² | 415 A | 324 A | 7.57 V (1.89%) | 392.4 V | 12.48 V (3.12%) | 9175.2 W | Drop High |
| 300 mm² | 477 A | 372 A | 6.05 V (1.51%) | 393.9 V | 9.99 V (2.5%) | 7340.2 W | Drop High |
| 400 mm² | 570 A | 445 A | 4.54 V (1.14%) | 395.5 V | 7.49 V (1.87%) | 5505.2 W | Drop High |
FAQ — Kabelarea för 700 Ampere vid 70 Meter (400V)
Vilken kabelarea krävs för 700A vid 70 meter (400V)?
För 700 Ampere över 70 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (2.27V / 0.57%).
Hur stor effekt motsvarar 700A vid 400V?
Det motsvarar 484.97 kW med en rekommenderad säkring på 700A.
Related Lengths & Currents (400V)
700A · 5m (400V)700A · 10m (400V)700A · 15m (400V)700A · 20m (400V)700A · 25m (400V)700A · 30m (400V)700A · 35m (400V)700A · 40m (400V)700A · 45m (400V)700A · 50m (400V)700A · 60m (400V)10A · 70m (400V)16A · 70m (400V)20A · 70m (400V)25A · 70m (400V)32A · 70m (400V)40A · 70m (400V)50A · 70m (400V)63A · 70m (400V)80A · 70m (400V)100A · 70m (400V)125A · 70m (400V)160A · 70m (400V)200A · 70m (400V)