Kabelarea för 700 Ampere vid 70 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 700 A över 70 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.27V (0.57%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.49V (1.87%)
Voltage at Load397.7 VLine Loss: 2752.6 W
Max Power & Breaker484.97 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1210.82 V (302.7%)0.0 V1997.29 V (499.32%)1468040.0 WDrop High
2.5 mm²24 A18 A726.49 V (181.62%)0.0 V1198.37 V (299.59%)880824.0 WDrop High
4 mm²32 A25 A454.06 V (113.51%)0.0 V748.98 V (187.25%)550515.0 WDrop High
6 mm²41 A32 A302.7 V (75.68%)97.3 V499.32 V (124.83%)367010.0 WDrop High
10 mm²57 A44 A181.62 V (45.41%)218.4 V299.59 V (74.9%)220206.0 WDrop High
16 mm²76 A59 A113.51 V (28.38%)286.5 V187.25 V (46.81%)137628.8 WDrop High
25 mm²101 A78 A72.65 V (18.16%)327.4 V119.84 V (29.96%)88082.4 WDrop High
35 mm²125 A97 A51.89 V (12.97%)348.1 V85.6 V (21.4%)62916.0 WDrop High
50 mm²151 A118 A36.32 V (9.08%)363.7 V59.92 V (14.98%)44041.2 WDrop High
70 mm²192 A150 A25.95 V (6.49%)374.1 V42.8 V (10.7%)31458.0 WDrop High
95 mm²232 A181 A19.12 V (4.78%)380.9 V31.54 V (7.88%)23179.6 WDrop High
120 mm²269 A210 A15.14 V (3.78%)384.9 V24.97 V (6.24%)18350.5 WDrop High
150 mm²309 A241 A12.11 V (3.03%)387.9 V19.97 V (4.99%)14680.4 WDrop High
185 mm²353 A275 A9.82 V (2.45%)390.2 V16.19 V (4.05%)11903.0 WDrop High
240 mm²415 A324 A7.57 V (1.89%)392.4 V12.48 V (3.12%)9175.2 WDrop High
300 mm²477 A372 A6.05 V (1.51%)393.9 V9.99 V (2.5%)7340.2 WDrop High
400 mm²570 A445 A4.54 V (1.14%)395.5 V7.49 V (1.87%)5505.2 WDrop High

FAQ — Kabelarea för 700 Ampere vid 70 Meter (400V)

Vilken kabelarea krävs för 700A vid 70 meter (400V)?

För 700 Ampere över 70 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (2.27V / 0.57%).

Hur stor effekt motsvarar 700A vid 400V?

Det motsvarar 484.97 kW med en rekommenderad säkring på 700A.