Kabelarea för 700 Ampere vid 50 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 700 A över 50 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.62V (0.41%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.35V (1.34%)
Voltage at Load398.4 VLine Loss: 1966.1 W
Max Power & Breaker484.97 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A864.87 V (216.22%)0.0 V1426.63 V (356.66%)1048600.0 WDrop High
2.5 mm²24 A18 A518.92 V (129.73%)0.0 V855.98 V (213.99%)629160.0 WDrop High
4 mm²32 A25 A324.33 V (81.08%)75.7 V534.99 V (133.75%)393225.0 WDrop High
6 mm²41 A32 A216.22 V (54.05%)183.8 V356.66 V (89.16%)262150.0 WDrop High
10 mm²57 A44 A129.73 V (32.43%)270.3 V213.99 V (53.5%)157290.0 WDrop High
16 mm²76 A59 A81.08 V (20.27%)318.9 V133.75 V (33.44%)98306.2 WDrop High
25 mm²101 A78 A51.89 V (12.97%)348.1 V85.6 V (21.4%)62916.0 WDrop High
35 mm²125 A97 A37.07 V (9.27%)362.9 V61.14 V (15.29%)44940.0 WDrop High
50 mm²151 A118 A25.95 V (6.49%)374.1 V42.8 V (10.7%)31458.0 WDrop High
70 mm²192 A150 A18.53 V (4.63%)381.5 V30.57 V (7.64%)22470.0 WDrop High
95 mm²232 A181 A13.66 V (3.41%)386.3 V22.53 V (5.63%)16556.8 WDrop High
120 mm²269 A210 A10.81 V (2.7%)389.2 V17.83 V (4.46%)13107.5 WDrop High
150 mm²309 A241 A8.65 V (2.16%)391.4 V14.27 V (3.57%)10486.0 WDrop High
185 mm²353 A275 A7.01 V (1.75%)393.0 V11.57 V (2.89%)8502.2 WDrop High
240 mm²415 A324 A5.41 V (1.35%)394.6 V8.92 V (2.23%)6553.7 WDrop High
300 mm²477 A372 A4.32 V (1.08%)395.7 V7.13 V (1.78%)5243.0 WDrop High
400 mm²570 A445 A3.24 V (0.81%)396.8 V5.35 V (1.34%)3932.2 WDrop High

FAQ — Kabelarea för 700 Ampere vid 50 Meter (400V)

Vilken kabelarea krävs för 700A vid 50 meter (400V)?

För 700 Ampere över 50 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (1.62V / 0.41%).

Hur stor effekt motsvarar 700A vid 400V?

Det motsvarar 484.97 kW med en rekommenderad säkring på 700A.