Kabelarea för 750 Ampere vid 10 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 750 A över 10 m vid 230V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.4V (0.17%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.32V (0.58%)
Voltage at Load229.6 VLine Loss: 300.9 W
Max Power & Breaker172.5 kW800A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 10m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 214.0 V (93.04%) | 16.0 V | 353.0 V (153.48%) | 160500.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 128.4 V (55.83%) | 101.6 V | 211.8 V (92.09%) | 96300.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 80.25 V (34.89%) | 149.8 V | 132.38 V (57.55%) | 60187.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 53.5 V (23.26%) | 176.5 V | 88.25 V (38.37%) | 40125.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 32.1 V (13.96%) | 197.9 V | 52.95 V (23.02%) | 24075.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 20.06 V (8.72%) | 209.9 V | 33.09 V (14.39%) | 15046.9 W | Drop High |
| 25 mm² | 101 A | 78 A | 12.84 V (5.58%) | 217.2 V | 21.18 V (9.21%) | 9630.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 9.17 V (3.99%) | 220.8 V | 15.13 V (6.58%) | 6878.6 W | Drop High |
| 50 mm² | 151 A | 118 A | 6.42 V (2.79%) | 223.6 V | 10.59 V (4.6%) | 4815.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 4.59 V (1.99%) | 225.4 V | 7.56 V (3.29%) | 3439.3 W | Drop High |
| 95 mm² | 232 A | 181 A | 3.38 V (1.47%) | 226.6 V | 5.57 V (2.42%) | 2534.2 W | Drop High |
| 120 mm² | 269 A | 210 A | 2.68 V (1.16%) | 227.3 V | 4.41 V (1.92%) | 2006.2 W | Drop High |
| 150 mm² | 309 A | 241 A | 2.14 V (0.93%) | 227.9 V | 3.53 V (1.53%) | 1605.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 1.74 V (0.75%) | 228.3 V | 2.86 V (1.24%) | 1301.4 W | Drop High |
| 240 mm² | 415 A | 324 A | 1.34 V (0.58%) | 228.7 V | 2.21 V (0.96%) | 1003.1 W | Drop High |
| 300 mm² | 477 A | 372 A | 1.07 V (0.47%) | 228.9 V | 1.76 V (0.77%) | 802.5 W | Drop High |
| 400 mm² | 570 A | 445 A | 0.8 V (0.35%) | 229.2 V | 1.32 V (0.58%) | 601.9 W | Drop High |
FAQ — Kabelarea för 750 Ampere vid 10 Meter (230V)
Vilken kabelarea krävs för 750A vid 10 meter (230V)?
För 750 Ampere över 10 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (0.4V / 0.17%).
Hur stor effekt motsvarar 750A vid 230V?
Det motsvarar 172.5 kW med en rekommenderad säkring på 800A.
Related Lengths & Currents (230V)
750A · 5m (230V)750A · 15m (230V)750A · 20m (230V)750A · 25m (230V)750A · 30m (230V)750A · 35m (230V)750A · 40m (230V)750A · 45m (230V)750A · 50m (230V)750A · 60m (230V)750A · 70m (230V)10A · 10m (230V)16A · 10m (230V)20A · 10m (230V)25A · 10m (230V)32A · 10m (230V)40A · 10m (230V)50A · 10m (230V)63A · 10m (230V)80A · 10m (230V)100A · 10m (230V)125A · 10m (230V)160A · 10m (230V)200A · 10m (230V)