Kabelarea för 750 Ampere vid 25 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 750 A över 25 m vid 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.0V (0.43%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.31V (1.44%)
Voltage at Load229.0 VLine Loss: 752.4 W
Max Power & Breaker172.5 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A535.0 V (232.61%)0.0 V882.5 V (383.7%)401250.0 WDrop High
2.5 mm²24 A18 A321.0 V (139.57%)0.0 V529.5 V (230.22%)240750.0 WDrop High
4 mm²32 A25 A200.62 V (87.23%)29.4 V330.94 V (143.89%)150468.7 WDrop High
6 mm²41 A32 A133.75 V (58.15%)96.2 V220.62 V (95.92%)100312.5 WDrop High
10 mm²57 A44 A80.25 V (34.89%)149.8 V132.38 V (57.55%)60187.5 WDrop High
16 mm²76 A59 A50.16 V (21.81%)179.8 V82.73 V (35.97%)37617.2 WDrop High
25 mm²101 A78 A32.1 V (13.96%)197.9 V52.95 V (23.02%)24075.0 WDrop High
35 mm²125 A97 A22.93 V (9.97%)207.1 V37.82 V (16.44%)17196.4 WDrop High
50 mm²151 A118 A16.05 V (6.98%)213.9 V26.47 V (11.51%)12037.5 WDrop High
70 mm²192 A150 A11.46 V (4.98%)218.5 V18.91 V (8.22%)8598.2 WDrop High
95 mm²232 A181 A8.45 V (3.67%)221.6 V13.93 V (6.06%)6335.5 WDrop High
120 mm²269 A210 A6.69 V (2.91%)223.3 V11.03 V (4.8%)5015.6 WDrop High
150 mm²309 A241 A5.35 V (2.33%)224.7 V8.82 V (3.84%)4012.5 WDrop High
185 mm²353 A275 A4.34 V (1.89%)225.7 V7.16 V (3.11%)3253.4 WDrop High
240 mm²415 A324 A3.34 V (1.45%)226.7 V5.52 V (2.4%)2507.8 WDrop High
300 mm²477 A372 A2.67 V (1.16%)227.3 V4.41 V (1.92%)2006.2 WDrop High
400 mm²570 A445 A2.01 V (0.87%)228.0 V3.31 V (1.44%)1504.7 WDrop High

FAQ — Kabelarea för 750 Ampere vid 25 Meter (230V)

Vilken kabelarea krävs för 750A vid 25 meter (230V)?

För 750 Ampere över 25 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (1.0V / 0.43%).

Hur stor effekt motsvarar 750A vid 230V?

Det motsvarar 172.5 kW med en rekommenderad säkring på 800A.