⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 800 Ampere vid 10 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 800 A över 10 m vid 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.43V (0.18%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.41V (0.61%)
Voltage at Load229.6 VLine Loss: 342.4 W
Max Power & Breaker184.0 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A228.27 V (99.25%)1.7 V376.53 V (163.71%)182613.3 WDrop High
2.5 mm²24 A18 A136.96 V (59.55%)93.0 V225.92 V (98.23%)109568.0 WDrop High
4 mm²32 A25 A85.6 V (37.22%)144.4 V141.2 V (61.39%)68480.0 WDrop High
6 mm²41 A32 A57.07 V (24.81%)172.9 V94.13 V (40.93%)45653.3 WDrop High
10 mm²57 A44 A34.24 V (14.89%)195.8 V56.48 V (24.56%)27392.0 WDrop High
16 mm²76 A59 A21.4 V (9.3%)208.6 V35.3 V (15.35%)17120.0 WDrop High
25 mm²101 A78 A13.7 V (5.95%)216.3 V22.59 V (9.82%)10956.8 WDrop High
35 mm²125 A97 A9.78 V (4.25%)220.2 V16.14 V (7.02%)7826.3 WDrop High
50 mm²151 A118 A6.85 V (2.98%)223.2 V11.3 V (4.91%)5478.4 WDrop High
70 mm²192 A150 A4.89 V (2.13%)225.1 V8.07 V (3.51%)3913.1 WDrop High
95 mm²232 A181 A3.6 V (1.57%)226.4 V5.95 V (2.58%)2883.4 WDrop High
120 mm²269 A210 A2.85 V (1.24%)227.1 V4.71 V (2.05%)2282.7 WDrop High
150 mm²309 A241 A2.28 V (0.99%)227.7 V3.77 V (1.64%)1826.1 WDrop High
185 mm²353 A275 A1.85 V (0.8%)228.1 V3.05 V (1.33%)1480.6 WDrop High
240 mm²415 A324 A1.43 V (0.62%)228.6 V2.35 V (1.02%)1141.3 WDrop High
300 mm²477 A372 A1.14 V (0.5%)228.9 V1.88 V (0.82%)913.1 WDrop High
400 mm²570 A445 A0.86 V (0.37%)229.1 V1.41 V (0.61%)684.8 WDrop High

FAQ — Kabelarea för 800 Ampere vid 10 Meter (230V)

Vilken kabelarea krävs för 800A vid 10 meter (230V)?

För 800 Ampere över 10 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (0.43V / 0.18%).

Hur stor effekt motsvarar 800A vid 230V?

Det motsvarar 184.0 kW med en rekommenderad säkring på 800A.