Kabelarea för 800 Ampere vid 60 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 800 A över 60 m vid 230V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.57V (1.11%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.47V (3.68%)
Voltage at Load227.4 VLine Loss: 2054.4 W
Max Power & Breaker184.0 kW800A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 60m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1369.6 V (595.48%) | 0.0 V | 2259.2 V (982.26%) | 1095680.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 821.76 V (357.29%) | 0.0 V | 1355.52 V (589.36%) | 657408.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 513.6 V (223.3%) | 0.0 V | 847.2 V (368.35%) | 410880.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 342.4 V (148.87%) | 0.0 V | 564.8 V (245.57%) | 273920.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 205.44 V (89.32%) | 24.6 V | 338.88 V (147.34%) | 164352.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 128.4 V (55.83%) | 101.6 V | 211.8 V (92.09%) | 102720.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 82.18 V (35.73%) | 147.8 V | 135.55 V (58.94%) | 65740.8 W | Drop High |
| 35 mm² | 125 A | 97 A | 58.7 V (25.52%) | 171.3 V | 96.82 V (42.1%) | 46957.7 W | Drop High |
| 50 mm² | 151 A | 118 A | 41.09 V (17.86%) | 188.9 V | 67.78 V (29.47%) | 32870.4 W | Drop High |
| 70 mm² | 192 A | 150 A | 29.35 V (12.76%) | 200.7 V | 48.41 V (21.05%) | 23478.9 W | Drop High |
| 95 mm² | 232 A | 181 A | 21.63 V (9.4%) | 208.4 V | 35.67 V (15.51%) | 17300.2 W | Drop High |
| 120 mm² | 269 A | 210 A | 17.12 V (7.44%) | 212.9 V | 28.24 V (12.28%) | 13696.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 13.7 V (5.95%) | 216.3 V | 22.59 V (9.82%) | 10956.8 W | Drop High |
| 185 mm² | 353 A | 275 A | 11.1 V (4.83%) | 218.9 V | 18.32 V (7.96%) | 8883.9 W | Drop High |
| 240 mm² | 415 A | 324 A | 8.56 V (3.72%) | 221.4 V | 14.12 V (6.14%) | 6848.0 W | Drop High |
| 300 mm² | 477 A | 372 A | 6.85 V (2.98%) | 223.2 V | 11.3 V (4.91%) | 5478.4 W | Drop High |
| 400 mm² | 570 A | 445 A | 5.14 V (2.23%) | 224.9 V | 8.47 V (3.68%) | 4108.8 W | Drop High |
FAQ — Kabelarea för 800 Ampere vid 60 Meter (230V)
Vilken kabelarea krävs för 800A vid 60 meter (230V)?
För 800 Ampere över 60 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (2.57V / 1.11%).
Hur stor effekt motsvarar 800A vid 230V?
Det motsvarar 184.0 kW med en rekommenderad säkring på 800A.
Related Lengths & Currents (230V)
800A · 5m (230V)800A · 10m (230V)800A · 15m (230V)800A · 20m (230V)800A · 25m (230V)800A · 30m (230V)800A · 35m (230V)800A · 40m (230V)800A · 45m (230V)800A · 50m (230V)800A · 70m (230V)10A · 60m (230V)16A · 60m (230V)20A · 60m (230V)25A · 60m (230V)32A · 60m (230V)40A · 60m (230V)50A · 60m (230V)63A · 60m (230V)80A · 60m (230V)100A · 60m (230V)125A · 60m (230V)160A · 60m (230V)200A · 60m (230V)