Kabelarea för 800 Ampere vid 300 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 800 A över 300 m vid 230V.

Copper Cable (≤3% Drop)4× 400 mm²Drop: 6.42V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 42.36V (18.42%)
Voltage at Load223.6 VLine Loss: 5136.0 W
Max Power & Breaker184.0 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6848.0 V (2977.39%)0.0 V11296.0 V (4911.3%)5478400.0 WDrop High
2.5 mm²24 A18 A4108.8 V (1786.43%)0.0 V6777.6 V (2946.78%)3287040.0 WDrop High
4 mm²32 A25 A2568.0 V (1116.52%)0.0 V4236.0 V (1841.74%)2054400.0 WDrop High
6 mm²41 A32 A1712.0 V (744.35%)0.0 V2824.0 V (1227.83%)1369600.0 WDrop High
10 mm²57 A44 A1027.2 V (446.61%)0.0 V1694.4 V (736.7%)821760.0 WDrop High
16 mm²76 A59 A642.0 V (279.13%)0.0 V1059.0 V (460.43%)513600.0 WDrop High
25 mm²101 A78 A410.88 V (178.64%)0.0 V677.76 V (294.68%)328704.0 WDrop High
35 mm²125 A97 A293.49 V (127.6%)0.0 V484.11 V (210.48%)234788.6 WDrop High
50 mm²151 A118 A205.44 V (89.32%)24.6 V338.88 V (147.34%)164352.0 WDrop High
70 mm²192 A150 A146.74 V (63.8%)83.3 V242.06 V (105.24%)117394.3 WDrop High
95 mm²232 A181 A108.13 V (47.01%)121.9 V178.36 V (77.55%)86501.1 WDrop High
120 mm²269 A210 A85.6 V (37.22%)144.4 V141.2 V (61.39%)68480.0 WDrop High
150 mm²309 A241 A68.48 V (29.77%)161.5 V112.96 V (49.11%)54784.0 WDrop High
185 mm²353 A275 A55.52 V (24.14%)174.5 V91.59 V (39.82%)44419.5 WDrop High
240 mm²415 A324 A42.8 V (18.61%)187.2 V70.6 V (30.7%)34240.0 WDrop High
300 mm²477 A372 A34.24 V (14.89%)195.8 V56.48 V (24.56%)27392.0 WDrop High
400 mm²570 A445 A25.68 V (11.17%)204.3 V42.36 V (18.42%)20544.0 WDrop High

FAQ — Kabelarea för 800 Ampere vid 300 Meter (230V)

Vilken kabelarea krävs för 800A vid 300 meter (230V)?

För 800 Ampere över 300 meter vid 230V rekommenderas 4× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.42V / 2.79%).

Hur stor effekt motsvarar 800A vid 230V?

Det motsvarar 184.0 kW med en rekommenderad säkring på 800A.