Kabelarea för 800 Ampere vid 400 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 800 A över 400 m vid 400V.

Copper Cable (≤3% Drop)3× 400 mm²Drop: 9.88V (2.47%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 48.91V (12.23%)
Voltage at Load390.1 VLine Loss: 13696.0 W
Max Power & Breaker554.26 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7907.39 V (1976.85%)0.0 V13043.5 V (3260.87%)10956800.0 WDrop High
2.5 mm²24 A18 A4744.43 V (1186.11%)0.0 V7826.1 V (1956.52%)6574080.0 WDrop High
4 mm²32 A25 A2965.27 V (741.32%)0.0 V4891.31 V (1222.83%)4108800.0 WDrop High
6 mm²41 A32 A1976.85 V (494.21%)0.0 V3260.87 V (815.22%)2739200.0 WDrop High
10 mm²57 A44 A1186.11 V (296.53%)0.0 V1956.52 V (489.13%)1643520.0 WDrop High
16 mm²76 A59 A741.32 V (185.33%)0.0 V1222.83 V (305.71%)1027200.0 WDrop High
25 mm²101 A78 A474.44 V (118.61%)0.0 V782.61 V (195.65%)657408.0 WDrop High
35 mm²125 A97 A338.89 V (84.72%)61.1 V559.01 V (139.75%)469577.1 WDrop High
50 mm²151 A118 A237.22 V (59.31%)162.8 V391.3 V (97.83%)328704.0 WDrop High
70 mm²192 A150 A169.44 V (42.36%)230.6 V279.5 V (69.88%)234788.6 WDrop High
95 mm²232 A181 A124.85 V (31.21%)275.1 V205.95 V (51.49%)173002.1 WDrop High
120 mm²269 A210 A98.84 V (24.71%)301.2 V163.04 V (40.76%)136960.0 WDrop High
150 mm²309 A241 A79.07 V (19.77%)320.9 V130.43 V (32.61%)109568.0 WDrop High
185 mm²353 A275 A64.11 V (16.03%)335.9 V105.76 V (26.44%)88838.9 WDrop High
240 mm²415 A324 A49.42 V (12.36%)350.6 V81.52 V (20.38%)68480.0 WDrop High
300 mm²477 A372 A39.54 V (9.88%)360.5 V65.22 V (16.3%)54784.0 WDrop High
400 mm²570 A445 A29.65 V (7.41%)370.3 V48.91 V (12.23%)41088.0 WDrop High

FAQ — Kabelarea för 800 Ampere vid 400 Meter (400V)

Vilken kabelarea krävs för 800A vid 400 meter (400V)?

För 800 Ampere över 400 meter vid 400V rekommenderas 3× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (9.88V / 2.47%).

Hur stor effekt motsvarar 800A vid 400V?

Det motsvarar 554.26 kW med en rekommenderad säkring på 800A.