🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

10 Amp Wire Size at 175 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 10 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)14 AWG2.08 mm² · Drop: 1.98%
Aluminum Wire (≤3% Drop)12 AWGDrop: 9.85V (2.05%)
Voltage at Load End470.5 VLoss: 9.51 V (164.6 W)
Power & Breaker (125%)8.31 kW13A Breaker Recommended

All AWG & kcmil Wire Gauges for 10 Amps at 175 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A9.51 V (1.98%)470.5 V15.68 V (3.27%)164.6 W✓ PASS (≤3%)
12 AWG3.31 mm²20 A5.97 V (1.24%)474.0 V9.85 V (2.05%)103.5 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A3.76 V (0.78%)476.2 V6.2 V (1.29%)65.1 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A2.36 V (0.49%)477.6 V3.9 V (0.81%)40.9 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.49 V (0.31%)478.5 V2.45 V (0.51%)25.7 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.93 V (0.19%)479.1 V1.54 V (0.32%)16.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.74 V (0.15%)479.3 V1.22 V (0.25%)12.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.59 V (0.12%)479.4 V0.97 V (0.2%)10.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.47 V (0.1%)479.5 V0.77 V (0.16%)8.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.37 V (0.08%)479.6 V0.61 V (0.13%)6.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.29 V (0.06%)479.7 V0.48 V (0.1%)5.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.23 V (0.05%)479.8 V0.38 V (0.08%)4.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.18 V (0.04%)479.8 V0.3 V (0.06%)3.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.16 V (0.03%)479.8 V0.26 V (0.05%)2.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.13 V (0.03%)479.9 V0.21 V (0.04%)2.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.11 V (0.02%)479.9 V0.18 V (0.04%)1.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.1 V (0.02%)479.9 V0.16 V (0.03%)1.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.08 V (0.02%)479.9 V0.13 V (0.03%)1.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.07 V (0.01%)479.9 V0.11 V (0.02%)1.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.05 V (0.01%)479.9 V0.09 V (0.02%)0.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.04 V (0.01%)480.0 V0.06 V (0.01%)0.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 10 amps at 175 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 10A load over 175 feet one-way at 480V (3-Phase), you need 14 AWG copper wire. This produces a voltage drop of 9.51V (1.98%) and delivers 470.5V at the load.

What size aluminum wire is required for 10 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 12 AWG to maintain voltage drop at 9.85V (2.05%).

What breaker size is needed for a 10A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (10A × 1.25 = 12.5A), which corresponds to a standard 13A circuit breaker.