⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

150 Amp Wire Size at 175 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 150 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 1.16%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 5.75V (1.2%)
Voltage at Load End474.5 VLoss: 5.54 V (1440.4 W)
Power & Breaker (125%)124.71 kW200A Breaker Recommended

All AWG & kcmil Wire Gauges for 150 Amps at 175 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A142.58 V (29.7%)337.4 V235.19 V (49.0%)37043.1 WDrop/Amp High
12 AWG3.31 mm²20 A89.6 V (18.67%)390.4 V147.79 V (30.79%)23277.8 WDrop/Amp High
10 AWG5.26 mm²30 A56.38 V (11.75%)423.6 V93.0 V (19.38%)14648.2 WDrop/Amp High
8 AWG8.37 mm²50 A35.43 V (7.38%)444.6 V58.45 V (12.18%)9205.5 WDrop/Amp High
6 AWG13.3 mm²65 A22.3 V (4.65%)457.7 V36.78 V (7.66%)5793.2 WDrop/Amp High
4 AWG21.15 mm²85 A14.02 V (2.92%)466.0 V23.13 V (4.82%)3643.0 WDrop/Amp High
3 AWG26.67 mm²100 A11.12 V (2.32%)468.9 V18.34 V (3.82%)2889.0 WDrop/Amp High
2 AWG33.62 mm²115 A8.82 V (1.84%)471.2 V14.55 V (3.03%)2291.8 WDrop/Amp High
1 AWG42.41 mm²130 A6.99 V (1.46%)473.0 V11.53 V (2.4%)1816.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.54 V (1.16%)474.5 V9.15 V (1.91%)1440.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A4.4 V (0.92%)475.6 V7.25 V (1.51%)1142.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A3.49 V (0.73%)476.5 V5.75 V (1.2%)906.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.77 V (0.58%)477.2 V4.56 V (0.95%)718.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.34 V (0.49%)477.7 V3.86 V (0.8%)608.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.95 V (0.41%)478.0 V3.22 V (0.67%)506.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.67 V (0.35%)478.3 V2.76 V (0.57%)434.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.46 V (0.3%)478.5 V2.41 V (0.5%)380.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.17 V (0.24%)478.8 V1.93 V (0.4%)304.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.98 V (0.2%)479.0 V1.61 V (0.34%)253.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.78 V (0.16%)479.2 V1.29 V (0.27%)202.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.59 V (0.12%)479.4 V0.97 V (0.2%)152.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 150 amps at 175 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 150A load over 175 feet one-way at 480V (3-Phase), you need 1/0 AWG copper wire. This produces a voltage drop of 5.54V (1.16%) and delivers 474.5V at the load.

What size aluminum wire is required for 150 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 5.75V (1.2%).

What breaker size is needed for a 150A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (150A × 1.25 = 187.5A), which corresponds to a standard 200A circuit breaker.