🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

100 Amp Wire Size at 200 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 100 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 2.8%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 6.97V (2.9%)
Voltage at Load End233.3 VLoss: 6.72 V (1164.1 W)
Power & Breaker (125%)41.57 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 100 Amps at 200 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A108.63 V (45.26%)131.4 V179.19 V (74.66%)18815.5 WDrop/Amp High
12 AWG3.31 mm²20 A68.26 V (28.44%)171.7 V112.6 V (46.92%)11823.7 WDrop/Amp High
10 AWG5.26 mm²30 A42.96 V (17.9%)197.0 V70.86 V (29.52%)7440.4 WDrop/Amp High
8 AWG8.37 mm²50 A27.0 V (11.25%)213.0 V44.53 V (18.55%)4675.8 WDrop/Amp High
6 AWG13.3 mm²65 A16.99 V (7.08%)223.0 V28.02 V (11.68%)2942.6 WDrop/Amp High
4 AWG21.15 mm²85 A10.68 V (4.45%)229.3 V17.62 V (7.34%)1850.4 WDrop/Amp High
3 AWG26.67 mm²100 A8.47 V (3.53%)231.5 V13.98 V (5.82%)1467.4 W~ ≤5%
2 AWG33.62 mm²115 A6.72 V (2.8%)233.3 V11.09 V (4.62%)1164.1 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A5.33 V (2.22%)234.7 V8.79 V (3.66%)922.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A4.22 V (1.76%)235.8 V6.97 V (2.9%)731.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.35 V (1.4%)236.6 V5.53 V (2.3%)580.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.66 V (1.11%)237.3 V4.38 V (1.83%)460.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.11 V (0.88%)237.9 V3.48 V (1.45%)365.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.78 V (0.74%)238.2 V2.94 V (1.23%)308.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.49 V (0.62%)238.5 V2.45 V (1.02%)257.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.27 V (0.53%)238.7 V2.1 V (0.88%)220.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.11 V (0.46%)238.9 V1.84 V (0.77%)193.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.89 V (0.37%)239.1 V1.47 V (0.61%)154.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.74 V (0.31%)239.3 V1.23 V (0.51%)128.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.59 V (0.25%)239.4 V0.98 V (0.41%)103.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.45 V (0.19%)239.6 V0.74 V (0.31%)77.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 100 amps at 200 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 100A load over 200 feet one-way at 240V (3-Phase), you need 2 AWG copper wire. This produces a voltage drop of 6.72V (2.8%) and delivers 233.3V at the load.

What size aluminum wire is required for 100 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 6.97V (2.9%).

What breaker size is needed for a 100A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (100A × 1.25 = 125.0A), which corresponds to a standard 125A circuit breaker.