400 Amp Wire Size at 200 Feet (240V Three-Phase (US Industrial Delta))
Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 400 A load over a 200 ft (61.0 m) one-way run.
Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 1.24%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.94V (1.23%)
Voltage at Load End237.0 VLoss: 2.97 V (2059.8 W)
Power & Breaker (125%)166.28 kW500A Breaker Recommended
All AWG & kcmil Wire Gauges for 400 Amps at 200 Feet (240V)
| Wire Gauge | Metric Area | NEC 75°C Cu Ampacity | Copper Voltage Drop | Load Voltage | Aluminum Drop | Line Loss ($I^2R$) | NEC Status |
|---|---|---|---|---|---|---|---|
| 14 AWG | 2.08 mm² | 15 A | 434.53 V (181.05%) | 0.0 V | 716.77 V (298.65%) | 301048.6 W | Drop/Amp High |
| 12 AWG | 3.31 mm² | 20 A | 273.06 V (113.77%) | 0.0 V | 450.41 V (187.67%) | 189178.6 W | Drop/Amp High |
| 10 AWG | 5.26 mm² | 30 A | 171.83 V (71.59%) | 68.2 V | 283.44 V (118.1%) | 119045.8 W | Drop/Amp High |
| 8 AWG | 8.37 mm² | 50 A | 107.98 V (44.99%) | 132.0 V | 178.12 V (74.22%) | 74812.6 W | Drop/Amp High |
| 6 AWG | 13.3 mm² | 65 A | 67.96 V (28.31%) | 172.0 V | 112.1 V (46.71%) | 47081.3 W | Drop/Amp High |
| 4 AWG | 21.15 mm² | 85 A | 42.73 V (17.81%) | 197.3 V | 70.49 V (29.37%) | 29606.7 W | Drop/Amp High |
| 3 AWG | 26.67 mm² | 100 A | 33.89 V (14.12%) | 206.1 V | 55.9 V (23.29%) | 23478.9 W | Drop/Amp High |
| 2 AWG | 33.62 mm² | 115 A | 26.88 V (11.2%) | 213.1 V | 44.34 V (18.48%) | 18625.3 W | Drop/Amp High |
| 1 AWG | 42.41 mm² | 130 A | 21.31 V (8.88%) | 218.7 V | 35.15 V (14.65%) | 14764.9 W | Drop/Amp High |
| 1/0 AWG | 53.49 mm² | 150 A | 16.9 V (7.04%) | 223.1 V | 27.87 V (11.61%) | 11706.5 W | Drop/Amp High |
| 2/0 AWG | 67.43 mm² | 175 A | 13.4 V (5.58%) | 226.6 V | 22.11 V (9.21%) | 9286.4 W | Drop/Amp High |
| 3/0 AWG | 85.01 mm² | 200 A | 10.63 V (4.43%) | 229.4 V | 17.54 V (7.31%) | 7366.0 W | Drop/Amp High |
| 4/0 AWG | 107.2 mm² | 230 A | 8.43 V (3.51%) | 231.6 V | 13.91 V (5.79%) | 5841.2 W | Drop/Amp High |
| 250 kcmil | 126.7 mm² | 255 A | 7.13 V (2.97%) | 232.9 V | 11.77 V (4.9%) | 4942.2 W | Drop/Amp High |
| 300 kcmil | 152.0 mm² | 285 A | 5.95 V (2.48%) | 234.1 V | 9.81 V (4.09%) | 4119.6 W | Drop/Amp High |
| 350 kcmil | 177.3 mm² | 310 A | 5.1 V (2.12%) | 234.9 V | 8.41 V (3.5%) | 3531.8 W | Drop/Amp High |
| 400 kcmil | 202.7 mm² | 335 A | 4.46 V (1.86%) | 235.5 V | 7.36 V (3.06%) | 3089.2 W | Drop/Amp High |
| 500 kcmil | 253.4 mm² | 380 A | 3.57 V (1.49%) | 236.4 V | 5.88 V (2.45%) | 2471.1 W | Drop/Amp High |
| 600 kcmil | 304.0 mm² | 420 A | 2.97 V (1.24%) | 237.0 V | 4.9 V (2.04%) | 2059.8 W | ✓ PASS (≤3%) |
| 750 kcmil | 380.0 mm² | 475 A | 2.38 V (0.99%) | 237.6 V | 3.92 V (1.63%) | 1647.8 W | ✓ PASS (≤3%) |
| 1000 kcmil | 506.7 mm² | 545 A | 1.78 V (0.74%) | 238.2 V | 2.94 V (1.23%) | 1235.8 W | ✓ PASS (≤3%) |
Frequently Asked Engineering Questions
What size copper wire do I need for 400 amps at 200 feet (240V)?
To stay within the NEC recommended 3% maximum voltage drop for a 400A load over 200 feet one-way at 240V (3-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 2.97V (1.24%) and delivers 237.0V at the load.
What size aluminum wire is required for 400 amps at 200 feet?
Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.94V (1.23%).
What breaker size is needed for a 400A continuous load?
Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (400A × 1.25 = 500.0A), which corresponds to a standard 500A circuit breaker.
Compare Other Distances & Amperages
400 Amp Wire Size by Distance (240V)
400A at 20 ft (240V)400A at 30 ft (240V)400A at 40 ft (240V)400A at 50 ft (240V)400A at 60 ft (240V)400A at 75 ft (240V)400A at 80 ft (240V)400A at 100 ft (240V)400A at 120 ft (240V)400A at 125 ft (240V)400A at 150 ft (240V)400A at 175 ft (240V)