🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 1000 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 42.47V (17.7%)
Voltage at Load End233.6 VLoss: 6.44 V (6436.5 W)
Power & Breaker (125%)240.0 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 1000 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A6271.85 V (2613.27%)0.0 V10345.62 V (4310.67%)6271846.2 WDrop/Amp High
12 AWG3.31 mm²20 A3941.22 V (1642.18%)0.0 V6501.17 V (2708.82%)3941220.5 WDrop/Amp High
10 AWG5.26 mm²30 A2480.12 V (1033.38%)0.0 V4091.04 V (1704.6%)2480121.7 WDrop/Amp High
8 AWG8.37 mm²50 A1558.59 V (649.41%)0.0 V2570.95 V (1071.23%)1558595.0 WDrop/Amp High
6 AWG13.3 mm²65 A980.86 V (408.69%)0.0 V1617.96 V (674.15%)980860.2 WDrop/Amp High
4 AWG21.15 mm²85 A616.81 V (257.0%)0.0 V1017.44 V (423.93%)616805.7 WDrop/Amp High
3 AWG26.67 mm²100 A489.14 V (203.81%)0.0 V806.86 V (336.19%)489142.9 WDrop/Amp High
2 AWG33.62 mm²115 A388.03 V (161.68%)0.0 V640.06 V (266.69%)388026.2 WDrop/Amp High
1 AWG42.41 mm²130 A307.6 V (128.17%)0.0 V507.4 V (211.42%)307602.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A243.89 V (101.62%)0.0 V402.3 V (167.62%)243885.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A193.47 V (80.61%)46.5 V319.13 V (132.97%)193466.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A153.46 V (63.94%)86.5 V253.13 V (105.47%)153457.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A121.69 V (50.71%)118.3 V200.74 V (83.64%)121692.5 WDrop/Amp High
250 kcmil126.7 mm²255 A102.96 V (42.9%)137.0 V169.84 V (70.77%)102963.2 WDrop/Amp High
300 kcmil152.0 mm²285 A85.83 V (35.76%)154.2 V141.57 V (58.99%)85825.3 WDrop/Amp High
350 kcmil177.3 mm²310 A73.58 V (30.66%)166.4 V121.37 V (50.57%)73578.3 WDrop/Amp High
400 kcmil202.7 mm²335 A64.36 V (26.82%)175.6 V106.16 V (44.23%)64358.4 WDrop/Amp High
500 kcmil253.4 mm²380 A51.48 V (21.45%)188.5 V84.92 V (35.38%)51481.6 WDrop/Amp High
600 kcmil304.0 mm²420 A42.91 V (17.88%)197.1 V70.79 V (29.49%)42912.6 WDrop/Amp High
750 kcmil380.0 mm²475 A34.33 V (14.3%)205.7 V56.63 V (23.6%)34330.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A25.75 V (10.73%)214.3 V42.47 V (17.7%)25745.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 1000 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 1000 feet one-way at 240V (1-Phase), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 6.44V (2.68%) and delivers 233.6V at the load.

What size aluminum wire is required for 1000 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 42.47V (17.7%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.