⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 175 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.94%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.43V (3.1%)
Voltage at Load End237.8 VLoss: 2.25 V (2252.8 W)
Power & Breaker (125%)240.0 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1097.57 V (457.32%)0.0 V1810.48 V (754.37%)1097573.1 WDrop/Amp High
12 AWG3.31 mm²20 A689.71 V (287.38%)0.0 V1137.71 V (474.04%)689713.6 WDrop/Amp High
10 AWG5.26 mm²30 A434.02 V (180.84%)0.0 V715.93 V (298.31%)434021.3 WDrop/Amp High
8 AWG8.37 mm²50 A272.75 V (113.65%)0.0 V449.92 V (187.47%)272754.1 WDrop/Amp High
6 AWG13.3 mm²65 A171.65 V (71.52%)68.3 V283.14 V (117.98%)171650.5 WDrop/Amp High
4 AWG21.15 mm²85 A107.94 V (44.98%)132.1 V178.05 V (74.19%)107941.0 WDrop/Amp High
3 AWG26.67 mm²100 A85.6 V (35.67%)154.4 V141.2 V (58.83%)85600.0 WDrop/Amp High
2 AWG33.62 mm²115 A67.9 V (28.29%)172.1 V112.01 V (46.67%)67904.6 WDrop/Amp High
1 AWG42.41 mm²130 A53.83 V (22.43%)186.2 V88.8 V (37.0%)53830.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A42.68 V (17.78%)197.3 V70.4 V (29.33%)42680.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A33.86 V (14.11%)206.1 V55.85 V (23.27%)33856.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A26.86 V (11.19%)213.1 V44.3 V (18.46%)26855.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A21.3 V (8.87%)218.7 V35.13 V (14.64%)21296.2 WDrop/Amp High
250 kcmil126.7 mm²255 A18.02 V (7.51%)222.0 V29.72 V (12.38%)18018.6 WDrop/Amp High
300 kcmil152.0 mm²285 A15.02 V (6.26%)225.0 V24.78 V (10.32%)15019.4 WDrop/Amp High
350 kcmil177.3 mm²310 A12.88 V (5.37%)227.1 V21.24 V (8.85%)12876.2 WDrop/Amp High
400 kcmil202.7 mm²335 A11.26 V (4.69%)228.7 V18.58 V (7.74%)11262.7 WDrop/Amp High
500 kcmil253.4 mm²380 A9.01 V (3.75%)231.0 V14.86 V (6.19%)9009.3 WDrop/Amp High
600 kcmil304.0 mm²420 A7.51 V (3.13%)232.5 V12.39 V (5.16%)7509.7 WDrop/Amp High
750 kcmil380.0 mm²475 A6.01 V (2.5%)234.0 V9.91 V (4.13%)6007.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.51 V (1.88%)235.5 V7.43 V (3.1%)4505.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 175 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.25V (0.94%) and delivers 237.8V at the load.

What size aluminum wire is required for 1000 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.43V (3.1%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.