⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 150 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.69%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.52V (2.3%)
Voltage at Load End238.3 VLoss: 1.67 V (2896.4 W)
Power & Breaker (125%)415.69 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A814.74 V (339.47%)0.0 V1343.93 V (559.97%)1411165.4 WDrop/Amp High
12 AWG3.31 mm²20 A511.98 V (213.32%)0.0 V844.53 V (351.89%)886774.6 WDrop/Amp High
10 AWG5.26 mm²30 A322.18 V (134.24%)0.0 V531.44 V (221.43%)558027.4 WDrop/Amp High
8 AWG8.37 mm²50 A202.47 V (84.36%)37.5 V333.98 V (139.16%)350683.9 WDrop/Amp High
6 AWG13.3 mm²65 A127.42 V (53.09%)112.6 V210.18 V (87.57%)220693.5 WDrop/Amp High
4 AWG21.15 mm²85 A80.13 V (33.39%)159.9 V132.17 V (55.07%)138781.3 WDrop/Amp High
3 AWG26.67 mm²100 A63.54 V (26.48%)176.5 V104.81 V (43.67%)110057.1 WDrop/Amp High
2 AWG33.62 mm²115 A50.41 V (21.0%)189.6 V83.15 V (34.64%)87305.9 WDrop/Amp High
1 AWG42.41 mm²130 A39.96 V (16.65%)200.0 V65.91 V (27.46%)69210.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A31.68 V (13.2%)208.3 V52.26 V (21.77%)54874.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A25.13 V (10.47%)214.9 V41.46 V (17.27%)43529.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A19.93 V (8.31%)220.1 V32.88 V (13.7%)34528.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.81 V (6.59%)224.2 V26.08 V (10.87%)27380.8 WDrop/Amp High
250 kcmil126.7 mm²255 A13.38 V (5.57%)226.6 V22.06 V (9.19%)23166.7 WDrop/Amp High
300 kcmil152.0 mm²285 A11.15 V (4.65%)228.9 V18.39 V (7.66%)19310.7 WDrop/Amp High
350 kcmil177.3 mm²310 A9.56 V (3.98%)230.4 V15.77 V (6.57%)16555.1 WDrop/Amp High
400 kcmil202.7 mm²335 A8.36 V (3.48%)231.6 V13.79 V (5.75%)14480.6 WDrop/Amp High
500 kcmil253.4 mm²380 A6.69 V (2.79%)233.3 V11.03 V (4.6%)11583.4 WDrop/Amp High
600 kcmil304.0 mm²420 A5.57 V (2.32%)234.4 V9.2 V (3.83%)9655.3 WDrop/Amp High
750 kcmil380.0 mm²475 A4.46 V (1.86%)235.5 V7.36 V (3.07%)7724.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.34 V (1.39%)236.7 V5.52 V (2.3%)5792.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 150 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.67V (0.69%) and delivers 238.3V at the load.

What size aluminum wire is required for 1000 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.52V (2.3%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.