🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 75 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.35%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.76V (1.15%)
Voltage at Load End239.2 VLoss: 0.83 V (1448.2 W)
Power & Breaker (125%)415.69 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A407.37 V (169.74%)0.0 V671.97 V (279.99%)705582.7 WDrop/Amp High
12 AWG3.31 mm²20 A255.99 V (106.66%)0.0 V422.26 V (175.94%)443387.3 WDrop/Amp High
10 AWG5.26 mm²30 A161.09 V (67.12%)78.9 V265.72 V (110.72%)279013.7 WDrop/Amp High
8 AWG8.37 mm²50 A101.23 V (42.18%)138.8 V166.99 V (69.58%)175341.9 WDrop/Amp High
6 AWG13.3 mm²65 A63.71 V (26.55%)176.3 V105.09 V (43.79%)110346.8 WDrop/Amp High
4 AWG21.15 mm²85 A40.06 V (16.69%)199.9 V66.08 V (27.54%)69390.6 WDrop/Amp High
3 AWG26.67 mm²100 A31.77 V (13.24%)208.2 V52.41 V (21.84%)55028.6 WDrop/Amp High
2 AWG33.62 mm²115 A25.2 V (10.5%)214.8 V41.57 V (17.32%)43652.9 WDrop/Amp High
1 AWG42.41 mm²130 A19.98 V (8.32%)220.0 V32.96 V (13.73%)34605.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.84 V (6.6%)224.2 V26.13 V (10.89%)27437.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.57 V (5.24%)227.4 V20.73 V (8.64%)21765.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.97 V (4.15%)230.0 V16.44 V (6.85%)17264.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.9 V (3.29%)232.1 V13.04 V (5.43%)13690.4 WDrop/Amp High
250 kcmil126.7 mm²255 A6.69 V (2.79%)233.3 V11.03 V (4.6%)11583.4 WDrop/Amp High
300 kcmil152.0 mm²285 A5.57 V (2.32%)234.4 V9.2 V (3.83%)9655.3 WDrop/Amp High
350 kcmil177.3 mm²310 A4.78 V (1.99%)235.2 V7.88 V (3.28%)8277.6 WDrop/Amp High
400 kcmil202.7 mm²335 A4.18 V (1.74%)235.8 V6.9 V (2.87%)7240.3 WDrop/Amp High
500 kcmil253.4 mm²380 A3.34 V (1.39%)236.7 V5.52 V (2.3%)5791.7 WDrop/Amp High
600 kcmil304.0 mm²420 A2.79 V (1.16%)237.2 V4.6 V (1.92%)4827.7 WDrop/Amp High
750 kcmil380.0 mm²475 A2.23 V (0.93%)237.8 V3.68 V (1.53%)3862.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.67 V (0.7%)238.3 V2.76 V (1.15%)2896.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 75 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.83V (0.35%) and delivers 239.2V at the load.

What size aluminum wire is required for 1000 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.76V (1.15%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.