🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 20 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.04%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.74V (0.15%)
Voltage at Load End479.8 VLoss: 0.23 V (386.2 W)
Power & Breaker (125%)831.38 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 20 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A108.63 V (22.63%)371.4 V179.19 V (37.33%)188155.4 WDrop/Amp High
12 AWG3.31 mm²20 A68.26 V (14.22%)411.7 V112.6 V (23.46%)118236.6 WDrop/Amp High
10 AWG5.26 mm²30 A42.96 V (8.95%)437.0 V70.86 V (14.76%)74403.7 WDrop/Amp High
8 AWG8.37 mm²50 A27.0 V (5.62%)453.0 V44.53 V (9.28%)46757.8 WDrop/Amp High
6 AWG13.3 mm²65 A16.99 V (3.54%)463.0 V28.02 V (5.84%)29425.8 WDrop/Amp High
4 AWG21.15 mm²85 A10.68 V (2.23%)469.3 V17.62 V (3.67%)18504.2 WDrop/Amp High
3 AWG26.67 mm²100 A8.47 V (1.77%)471.5 V13.98 V (2.91%)14674.3 WDrop/Amp High
2 AWG33.62 mm²115 A6.72 V (1.4%)473.3 V11.09 V (2.31%)11640.8 WDrop/Amp High
1 AWG42.41 mm²130 A5.33 V (1.11%)474.7 V8.79 V (1.83%)9228.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.22 V (0.88%)475.8 V6.97 V (1.45%)7316.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.35 V (0.7%)476.6 V5.53 V (1.15%)5804.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.66 V (0.55%)477.3 V4.38 V (0.91%)4603.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.11 V (0.44%)477.9 V3.48 V (0.72%)3650.8 WDrop/Amp High
250 kcmil126.7 mm²255 A1.78 V (0.37%)478.2 V2.94 V (0.61%)3088.9 WDrop/Amp High
300 kcmil152.0 mm²285 A1.49 V (0.31%)478.5 V2.45 V (0.51%)2574.8 WDrop/Amp High
350 kcmil177.3 mm²310 A1.27 V (0.27%)478.7 V2.1 V (0.44%)2207.4 WDrop/Amp High
400 kcmil202.7 mm²335 A1.11 V (0.23%)478.9 V1.84 V (0.38%)1930.8 WDrop/Amp High
500 kcmil253.4 mm²380 A0.89 V (0.19%)479.1 V1.47 V (0.31%)1544.4 WDrop/Amp High
600 kcmil304.0 mm²420 A0.74 V (0.15%)479.3 V1.23 V (0.26%)1287.4 WDrop/Amp High
750 kcmil380.0 mm²475 A0.59 V (0.12%)479.4 V0.98 V (0.2%)1029.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.45 V (0.09%)479.6 V0.74 V (0.15%)772.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 20 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 20 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.23V (0.04%) and delivers 479.8V at the load.

What size aluminum wire is required for 1000 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.74V (0.15%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.