⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 40 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.1%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.47V (0.31%)
Voltage at Load End479.6 VLoss: 0.45 V (772.4 W)
Power & Breaker (125%)831.38 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 40 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A217.26 V (45.26%)262.7 V358.38 V (74.66%)376310.8 WDrop/Amp High
12 AWG3.31 mm²20 A136.53 V (28.44%)343.5 V225.21 V (46.92%)236473.2 WDrop/Amp High
10 AWG5.26 mm²30 A85.91 V (17.9%)394.1 V141.72 V (29.52%)148807.3 WDrop/Amp High
8 AWG8.37 mm²50 A53.99 V (11.25%)426.0 V89.06 V (18.55%)93515.7 WDrop/Amp High
6 AWG13.3 mm²65 A33.98 V (7.08%)446.0 V56.05 V (11.68%)58851.6 WDrop/Amp High
4 AWG21.15 mm²85 A21.37 V (4.45%)458.6 V35.25 V (7.34%)37008.3 WDrop/Amp High
3 AWG26.67 mm²100 A16.94 V (3.53%)463.1 V27.95 V (5.82%)29348.6 WDrop/Amp High
2 AWG33.62 mm²115 A13.44 V (2.8%)466.6 V22.17 V (4.62%)23281.6 WDrop/Amp High
1 AWG42.41 mm²130 A10.66 V (2.22%)469.3 V17.58 V (3.66%)18456.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.45 V (1.76%)471.6 V13.94 V (2.9%)14633.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.7 V (1.4%)473.3 V11.05 V (2.3%)11608.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.32 V (1.11%)474.7 V8.77 V (1.83%)9207.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.22 V (0.88%)475.8 V6.95 V (1.45%)7301.6 WDrop/Amp High
250 kcmil126.7 mm²255 A3.57 V (0.74%)476.4 V5.88 V (1.23%)6177.8 WDrop/Amp High
300 kcmil152.0 mm²285 A2.97 V (0.62%)477.0 V4.9 V (1.02%)5149.5 WDrop/Amp High
350 kcmil177.3 mm²310 A2.55 V (0.53%)477.5 V4.2 V (0.88%)4414.7 WDrop/Amp High
400 kcmil202.7 mm²335 A2.23 V (0.46%)477.8 V3.68 V (0.77%)3861.5 WDrop/Amp High
500 kcmil253.4 mm²380 A1.78 V (0.37%)478.2 V2.94 V (0.61%)3088.9 WDrop/Amp High
600 kcmil304.0 mm²420 A1.49 V (0.31%)478.5 V2.45 V (0.51%)2574.8 WDrop/Amp High
750 kcmil380.0 mm²475 A1.19 V (0.25%)478.8 V1.96 V (0.41%)2059.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.89 V (0.19%)479.1 V1.47 V (0.31%)1544.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 40 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 40 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.45V (0.1%) and delivers 479.6V at the load.

What size aluminum wire is required for 1000 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.47V (0.31%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.