🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 350 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.88%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 12.87V (6.19%)
Voltage at Load End204.1 VLoss: 3.9 V (6758.3 W)
Power & Breaker (125%)360.27 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 350 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1901.05 V (913.97%)0.0 V3135.85 V (1507.62%)3292719.2 WDrop/Amp High
12 AWG3.31 mm²20 A1194.62 V (574.34%)0.0 V1970.56 V (947.39%)2069140.8 WDrop/Amp High
10 AWG5.26 mm²30 A751.75 V (361.42%)0.0 V1240.03 V (596.17%)1302063.9 WDrop/Amp High
8 AWG8.37 mm²50 A472.42 V (227.13%)0.0 V779.28 V (374.65%)818262.4 WDrop/Amp High
6 AWG13.3 mm²65 A297.31 V (142.94%)0.0 V490.42 V (235.78%)514951.6 WDrop/Amp High
4 AWG21.15 mm²85 A186.96 V (89.88%)21.0 V308.4 V (148.27%)323823.0 WDrop/Amp High
3 AWG26.67 mm²100 A148.26 V (71.28%)59.7 V244.57 V (117.58%)256800.0 WDrop/Amp High
2 AWG33.62 mm²115 A117.61 V (56.55%)90.4 V194.01 V (93.27%)203713.7 WDrop/Amp High
1 AWG42.41 mm²130 A93.24 V (44.83%)114.8 V153.8 V (73.94%)161491.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A73.92 V (35.54%)134.1 V121.94 V (58.62%)128039.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A58.64 V (28.19%)149.4 V96.73 V (46.51%)101569.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A46.51 V (22.36%)161.5 V76.73 V (36.89%)80565.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A36.89 V (17.73%)171.1 V60.84 V (29.25%)63888.6 WDrop/Amp High
250 kcmil126.7 mm²255 A31.21 V (15.0%)176.8 V51.48 V (24.75%)54055.7 WDrop/Amp High
300 kcmil152.0 mm²285 A26.01 V (12.51%)182.0 V42.91 V (20.63%)45058.3 WDrop/Amp High
350 kcmil177.3 mm²310 A22.3 V (10.72%)185.7 V36.79 V (17.69%)38628.6 WDrop/Amp High
400 kcmil202.7 mm²335 A19.51 V (9.38%)188.5 V32.18 V (15.47%)33788.1 WDrop/Amp High
500 kcmil253.4 mm²380 A15.6 V (7.5%)192.4 V25.74 V (12.38%)27027.8 WDrop/Amp High
600 kcmil304.0 mm²420 A13.01 V (6.25%)195.0 V21.46 V (10.32%)22529.1 WDrop/Amp High
750 kcmil380.0 mm²475 A10.41 V (5.0%)197.6 V17.16 V (8.25%)18023.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A7.8 V (3.75%)200.2 V12.87 V (6.19%)13516.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 350 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 350 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.9V (1.88%) and delivers 204.1V at the load.

What size aluminum wire is required for 1000 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 12.87V (6.19%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.