⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 450 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)33× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.93%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 19.11V (159.26%)
Voltage at Load End11.7 VLoss: 0.35 V (351.1 W)
Power & Breaker (125%)12.0 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 450 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2822.33 V (23519.42%)0.0 V4655.53 V (38796.06%)2822330.8 WDrop/Amp High
12 AWG3.31 mm²20 A1773.55 V (14779.58%)0.0 V2925.53 V (24379.4%)1773549.2 WDrop/Amp High
10 AWG5.26 mm²30 A1116.05 V (9300.46%)0.0 V1840.97 V (15341.41%)1116054.8 WDrop/Amp High
8 AWG8.37 mm²50 A701.37 V (5844.73%)0.0 V1156.93 V (9641.08%)701367.7 WDrop/Amp High
6 AWG13.3 mm²65 A441.39 V (3678.23%)0.0 V728.08 V (6067.35%)441387.1 WDrop/Amp High
4 AWG21.15 mm²85 A277.56 V (2313.02%)0.0 V457.85 V (3815.4%)277562.6 WDrop/Amp High
3 AWG26.67 mm²100 A220.11 V (1834.29%)0.0 V363.09 V (3025.71%)220114.3 WDrop/Amp High
2 AWG33.62 mm²115 A174.61 V (1455.1%)0.0 V288.03 V (2400.23%)174611.8 WDrop/Amp High
1 AWG42.41 mm²130 A138.42 V (1153.51%)0.0 V228.33 V (1902.75%)138421.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A109.75 V (914.57%)0.0 V181.03 V (1508.61%)109748.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A87.06 V (725.5%)0.0 V143.61 V (1196.73%)87059.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A69.06 V (575.47%)0.0 V113.91 V (949.25%)69056.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A54.76 V (456.35%)0.0 V90.33 V (752.76%)54761.6 WDrop/Amp High
250 kcmil126.7 mm²255 A46.33 V (386.11%)0.0 V76.43 V (636.9%)46333.4 WDrop/Amp High
300 kcmil152.0 mm²285 A38.62 V (321.84%)0.0 V63.71 V (530.89%)38621.4 WDrop/Amp High
350 kcmil177.3 mm²310 A33.11 V (275.92%)0.0 V54.62 V (455.14%)33110.3 WDrop/Amp High
400 kcmil202.7 mm²335 A28.96 V (241.34%)0.0 V47.77 V (398.1%)28961.3 WDrop/Amp High
500 kcmil253.4 mm²380 A23.17 V (193.06%)0.0 V38.21 V (318.45%)23166.7 WDrop/Amp High
600 kcmil304.0 mm²420 A19.31 V (160.92%)0.0 V31.85 V (265.45%)19310.7 WDrop/Amp High
750 kcmil380.0 mm²475 A15.45 V (128.74%)0.0 V25.48 V (212.36%)15448.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A11.59 V (96.55%)0.4 V19.11 V (159.26%)11585.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 450 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 450 feet one-way at 12V (DC), you need 33× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.93%) and delivers 11.7V at the load.

What size aluminum wire is required for 1000 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 19.11V (159.26%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.