⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 500 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 21.23V (17.7%)
Voltage at Load End116.8 VLoss: 3.22 V (3218.2 W)
Power & Breaker (125%)120.0 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 500 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3135.92 V (2613.27%)0.0 V5172.81 V (4310.67%)3135923.1 WDrop/Amp High
12 AWG3.31 mm²20 A1970.61 V (1642.18%)0.0 V3250.59 V (2708.82%)1970610.3 WDrop/Amp High
10 AWG5.26 mm²30 A1240.06 V (1033.38%)0.0 V2045.52 V (1704.6%)1240060.8 WDrop/Amp High
8 AWG8.37 mm²50 A779.3 V (649.41%)0.0 V1285.48 V (1071.23%)779297.5 WDrop/Amp High
6 AWG13.3 mm²65 A490.43 V (408.69%)0.0 V808.98 V (674.15%)490430.1 WDrop/Amp High
4 AWG21.15 mm²85 A308.4 V (257.0%)0.0 V508.72 V (423.93%)308402.8 WDrop/Amp High
3 AWG26.67 mm²100 A244.57 V (203.81%)0.0 V403.43 V (336.19%)244571.4 WDrop/Amp High
2 AWG33.62 mm²115 A194.01 V (161.68%)0.0 V320.03 V (266.69%)194013.1 WDrop/Amp High
1 AWG42.41 mm²130 A153.8 V (128.17%)0.0 V253.7 V (211.42%)153801.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A121.94 V (101.62%)0.0 V201.15 V (167.62%)121942.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A96.73 V (80.61%)23.3 V159.56 V (132.97%)96733.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A76.73 V (63.94%)43.3 V126.57 V (105.47%)76728.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A60.85 V (50.71%)59.2 V100.37 V (83.64%)60846.3 WDrop/Amp High
250 kcmil126.7 mm²255 A51.48 V (42.9%)68.5 V84.92 V (70.77%)51481.6 WDrop/Amp High
300 kcmil152.0 mm²285 A42.91 V (35.76%)77.1 V70.79 V (58.99%)42912.6 WDrop/Amp High
350 kcmil177.3 mm²310 A36.79 V (30.66%)83.2 V60.68 V (50.57%)36789.2 WDrop/Amp High
400 kcmil202.7 mm²335 A32.18 V (26.82%)87.8 V53.08 V (44.23%)32179.2 WDrop/Amp High
500 kcmil253.4 mm²380 A25.74 V (21.45%)94.3 V42.46 V (35.38%)25740.8 WDrop/Amp High
600 kcmil304.0 mm²420 A21.46 V (17.88%)98.5 V35.39 V (29.49%)21456.3 WDrop/Amp High
750 kcmil380.0 mm²475 A17.17 V (14.3%)102.8 V28.31 V (23.6%)17165.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A12.87 V (10.73%)107.1 V21.23 V (17.7%)12872.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 500 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 500 feet one-way at 120V (1-Phase), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.22V (2.68%) and delivers 116.8V at the load.

What size aluminum wire is required for 1000 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 21.23V (17.7%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.