⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 500 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.33%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 18.39V (7.66%)
Voltage at Load End234.4 VLoss: 5.58 V (9654.7 W)
Power & Breaker (125%)415.69 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 500 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2715.79 V (1131.58%)0.0 V4479.78 V (1866.58%)4703884.6 WDrop/Amp High
12 AWG3.31 mm²20 A1706.6 V (711.08%)0.0 V2815.09 V (1172.95%)2955915.4 WDrop/Amp High
10 AWG5.26 mm²30 A1073.92 V (447.47%)0.0 V1771.47 V (738.11%)1860091.3 WDrop/Amp High
8 AWG8.37 mm²50 A674.89 V (281.2%)0.0 V1113.26 V (463.86%)1168946.2 WDrop/Amp High
6 AWG13.3 mm²65 A424.72 V (176.97%)0.0 V700.6 V (291.92%)735645.1 WDrop/Amp High
4 AWG21.15 mm²85 A267.08 V (111.29%)0.0 V440.56 V (183.57%)462604.3 WDrop/Amp High
3 AWG26.67 mm²100 A211.81 V (88.25%)28.2 V349.38 V (145.57%)366857.1 WDrop/Amp High
2 AWG33.62 mm²115 A168.02 V (70.01%)72.0 V277.15 V (115.48%)291019.6 WDrop/Amp High
1 AWG42.41 mm²130 A133.2 V (55.5%)106.8 V219.71 V (91.55%)230702.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A105.61 V (44.0%)134.4 V174.2 V (72.58%)182914.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A83.77 V (34.91%)156.2 V138.19 V (57.58%)145099.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A66.45 V (27.69%)173.6 V109.61 V (45.67%)115093.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A52.69 V (21.96%)187.3 V86.92 V (36.22%)91269.4 WDrop/Amp High
250 kcmil126.7 mm²255 A44.58 V (18.58%)195.4 V73.54 V (30.64%)77222.4 WDrop/Amp High
300 kcmil152.0 mm²285 A37.16 V (15.48%)202.8 V61.3 V (25.54%)64368.9 WDrop/Amp High
350 kcmil177.3 mm²310 A31.86 V (13.28%)208.1 V52.55 V (21.9%)55183.8 WDrop/Amp High
400 kcmil202.7 mm²335 A27.87 V (11.61%)212.1 V45.97 V (19.15%)48268.8 WDrop/Amp High
500 kcmil253.4 mm²380 A22.29 V (9.29%)217.7 V36.77 V (15.32%)38611.2 WDrop/Amp High
600 kcmil304.0 mm²420 A18.58 V (7.74%)221.4 V30.65 V (12.77%)32184.5 WDrop/Amp High
750 kcmil380.0 mm²475 A14.87 V (6.19%)225.1 V24.52 V (10.22%)25747.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A11.15 V (4.65%)228.9 V18.39 V (7.66%)19309.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 500 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 500 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.58V (2.33%) and delivers 234.4V at the load.

What size aluminum wire is required for 1000 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 18.39V (7.66%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.