🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 750 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 31.85V (13.27%)
Voltage at Load End233.6 VLoss: 6.44 V (6436.5 W)
Power & Breaker (125%)240.0 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4703.88 V (1959.95%)0.0 V7759.21 V (3233.0%)4703884.6 WDrop/Amp High
12 AWG3.31 mm²20 A2955.92 V (1231.63%)0.0 V4875.88 V (2031.62%)2955915.4 WDrop/Amp High
10 AWG5.26 mm²30 A1860.09 V (775.04%)0.0 V3068.28 V (1278.45%)1860091.3 WDrop/Amp High
8 AWG8.37 mm²50 A1168.95 V (487.06%)0.0 V1928.22 V (803.42%)1168946.2 WDrop/Amp High
6 AWG13.3 mm²65 A735.65 V (306.52%)0.0 V1213.47 V (505.61%)735645.1 WDrop/Amp High
4 AWG21.15 mm²85 A462.6 V (192.75%)0.0 V763.08 V (317.95%)462604.3 WDrop/Amp High
3 AWG26.67 mm²100 A366.86 V (152.86%)0.0 V605.14 V (252.14%)366857.1 WDrop/Amp High
2 AWG33.62 mm²115 A291.02 V (121.26%)0.0 V480.05 V (200.02%)291019.6 WDrop/Amp High
1 AWG42.41 mm²130 A230.7 V (96.13%)9.3 V380.55 V (158.56%)230702.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A182.91 V (76.21%)57.1 V301.72 V (125.72%)182914.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A145.1 V (60.46%)94.9 V239.35 V (99.73%)145099.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A115.09 V (47.96%)124.9 V189.85 V (79.1%)115093.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A91.27 V (38.03%)148.7 V150.55 V (62.73%)91269.4 WDrop/Amp High
250 kcmil126.7 mm²255 A77.22 V (32.18%)162.8 V127.38 V (53.08%)77222.4 WDrop/Amp High
300 kcmil152.0 mm²285 A64.37 V (26.82%)175.6 V106.18 V (44.24%)64368.9 WDrop/Amp High
350 kcmil177.3 mm²310 A55.18 V (22.99%)184.8 V91.03 V (37.93%)55183.8 WDrop/Amp High
400 kcmil202.7 mm²335 A48.27 V (20.11%)191.7 V79.62 V (33.18%)48268.8 WDrop/Amp High
500 kcmil253.4 mm²380 A38.61 V (16.09%)201.4 V63.69 V (26.54%)38611.2 WDrop/Amp High
600 kcmil304.0 mm²420 A32.18 V (13.41%)207.8 V53.09 V (22.12%)32184.5 WDrop/Amp High
750 kcmil380.0 mm²475 A25.75 V (10.73%)214.3 V42.47 V (17.7%)25747.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A19.31 V (8.05%)220.7 V31.85 V (13.27%)19309.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 750 feet one-way at 240V (1-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 6.44V (2.68%) and delivers 233.6V at the load.

What size aluminum wire is required for 1000 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 31.85V (13.27%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.