⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 125 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 1.93%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 4.79V (2.0%)
Voltage at Load End235.4 VLoss: 4.62 V (880.3 W)
Power & Breaker (125%)45.73 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 125 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A74.68 V (31.12%)165.3 V123.19 V (51.33%)14229.3 WDrop/Amp High
12 AWG3.31 mm²20 A46.93 V (19.55%)193.1 V77.41 V (32.26%)8941.6 WDrop/Amp High
10 AWG5.26 mm²30 A29.53 V (12.31%)210.5 V48.72 V (20.3%)5626.8 WDrop/Amp High
8 AWG8.37 mm²50 A18.56 V (7.73%)221.4 V30.61 V (12.76%)3536.1 WDrop/Amp High
6 AWG13.3 mm²65 A11.68 V (4.87%)228.3 V19.27 V (8.03%)2225.3 WDrop/Amp High
4 AWG21.15 mm²85 A7.34 V (3.06%)232.7 V12.12 V (5.05%)1399.4 WDrop/Amp High
3 AWG26.67 mm²100 A5.82 V (2.43%)234.2 V9.61 V (4.0%)1109.7 WDrop/Amp High
2 AWG33.62 mm²115 A4.62 V (1.93%)235.4 V7.62 V (3.18%)880.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.66 V (1.53%)236.3 V6.04 V (2.52%)697.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.9 V (1.21%)237.1 V4.79 V (2.0%)553.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.3 V (0.96%)237.7 V3.8 V (1.58%)438.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.83 V (0.76%)238.2 V3.01 V (1.26%)348.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.45 V (0.6%)238.6 V2.39 V (1.0%)276.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.23 V (0.51%)238.8 V2.02 V (0.84%)233.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.02 V (0.43%)239.0 V1.69 V (0.7%)194.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.88 V (0.37%)239.1 V1.45 V (0.6%)166.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.77 V (0.32%)239.2 V1.26 V (0.53%)146.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.61 V (0.26%)239.4 V1.01 V (0.42%)116.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.51 V (0.21%)239.5 V0.84 V (0.35%)97.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.41 V (0.17%)239.6 V0.67 V (0.28%)77.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.31 V (0.13%)239.7 V0.51 V (0.21%)58.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 125 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 125 feet one-way at 240V (3-Phase), you need 2 AWG copper wire. This produces a voltage drop of 4.62V (1.93%) and delivers 235.4V at the load.

What size aluminum wire is required for 110 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 4.79V (2.0%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.