⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 175 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 2.7%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 6.71V (2.79%)
Voltage at Load End233.5 VLoss: 6.47 V (1232.5 W)
Power & Breaker (125%)45.73 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A104.56 V (43.57%)135.4 V172.47 V (71.86%)19921.0 WDrop/Amp High
12 AWG3.31 mm²20 A65.7 V (27.38%)174.3 V108.38 V (45.16%)12518.3 WDrop/Amp High
10 AWG5.26 mm²30 A41.35 V (17.23%)198.7 V68.2 V (28.42%)7877.5 WDrop/Amp High
8 AWG8.37 mm²50 A25.98 V (10.83%)214.0 V42.86 V (17.86%)4950.5 WDrop/Amp High
6 AWG13.3 mm²65 A16.35 V (6.81%)223.6 V26.97 V (11.24%)3115.5 WDrop/Amp High
4 AWG21.15 mm²85 A10.28 V (4.28%)229.7 V16.96 V (7.07%)1959.1 WDrop/Amp High
3 AWG26.67 mm²100 A8.15 V (3.4%)231.8 V13.45 V (5.6%)1553.6 WDrop/Amp High
2 AWG33.62 mm²115 A6.47 V (2.7%)233.5 V10.67 V (4.45%)1232.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A5.13 V (2.14%)234.9 V8.46 V (3.52%)977.0 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A4.07 V (1.69%)235.9 V6.71 V (2.79%)774.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.23 V (1.34%)236.8 V5.32 V (2.22%)614.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.56 V (1.07%)237.4 V4.22 V (1.76%)487.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.03 V (0.85%)238.0 V3.35 V (1.39%)386.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.72 V (0.72%)238.3 V2.83 V (1.18%)327.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.43 V (0.6%)238.6 V2.36 V (0.98%)272.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.23 V (0.51%)238.8 V2.02 V (0.84%)233.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.07 V (0.45%)238.9 V1.77 V (0.74%)204.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.86 V (0.36%)239.1 V1.42 V (0.59%)163.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.72 V (0.3%)239.3 V1.18 V (0.49%)136.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.57 V (0.24%)239.4 V0.94 V (0.39%)109.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.43 V (0.18%)239.6 V0.71 V (0.29%)81.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 175 feet one-way at 240V (3-Phase), you need 2 AWG copper wire. This produces a voltage drop of 6.47V (2.7%) and delivers 233.5V at the load.

What size aluminum wire is required for 110 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 6.71V (2.79%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.