⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 30 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 0.46%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 1.15V (0.48%)
Voltage at Load End238.9 VLoss: 1.11 V (211.3 W)
Power & Breaker (125%)45.73 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A17.92 V (7.47%)222.1 V29.57 V (12.32%)3415.0 WDrop/Amp High
12 AWG3.31 mm²20 A11.26 V (4.69%)228.7 V18.58 V (7.74%)2146.0 WDrop/Amp High
10 AWG5.26 mm²30 A7.09 V (2.95%)232.9 V11.69 V (4.87%)1350.4 WDrop/Amp High
8 AWG8.37 mm²50 A4.45 V (1.86%)235.5 V7.35 V (3.06%)848.7 WDrop/Amp High
6 AWG13.3 mm²65 A2.8 V (1.17%)237.2 V4.62 V (1.93%)534.1 WDrop/Amp High
4 AWG21.15 mm²85 A1.76 V (0.73%)238.2 V2.91 V (1.21%)335.9 WDrop/Amp High
3 AWG26.67 mm²100 A1.4 V (0.58%)238.6 V2.31 V (0.96%)266.3 WDrop/Amp High
2 AWG33.62 mm²115 A1.11 V (0.46%)238.9 V1.83 V (0.76%)211.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.88 V (0.37%)239.1 V1.45 V (0.6%)167.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.7 V (0.29%)239.3 V1.15 V (0.48%)132.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.55 V (0.23%)239.4 V0.91 V (0.38%)105.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.44 V (0.18%)239.6 V0.72 V (0.3%)83.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.35 V (0.14%)239.7 V0.57 V (0.24%)66.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.29 V (0.12%)239.7 V0.49 V (0.2%)56.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.25 V (0.1%)239.8 V0.4 V (0.17%)46.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.21 V (0.09%)239.8 V0.35 V (0.14%)40.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.18 V (0.08%)239.8 V0.3 V (0.13%)35.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.15 V (0.06%)239.9 V0.24 V (0.1%)28.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.12 V (0.05%)239.9 V0.2 V (0.08%)23.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.1 V (0.04%)239.9 V0.16 V (0.07%)18.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.07 V (0.03%)239.9 V0.12 V (0.05%)14.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 30 feet one-way at 240V (3-Phase), you need 2 AWG copper wire. This produces a voltage drop of 1.11V (0.46%) and delivers 238.9V at the load.

What size aluminum wire is required for 110 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 1.15V (0.48%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.