🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 225 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 2.48%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 6.17V (2.57%)
Voltage at Load End234.1 VLoss: 5.94 V (1286.1 W)
Power & Breaker (125%)51.96 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 225 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A152.76 V (63.65%)87.2 V251.99 V (104.99%)33074.2 WDrop/Amp High
12 AWG3.31 mm²20 A96.0 V (40.0%)144.0 V158.35 V (65.98%)20783.8 WDrop/Amp High
10 AWG5.26 mm²30 A60.41 V (25.17%)179.6 V99.65 V (41.52%)13078.8 WDrop/Amp High
8 AWG8.37 mm²50 A37.96 V (15.82%)202.0 V62.62 V (26.09%)8219.2 WDrop/Amp High
6 AWG13.3 mm²65 A23.89 V (9.95%)216.1 V39.41 V (16.42%)5172.5 WDrop/Amp High
4 AWG21.15 mm²85 A15.02 V (6.26%)225.0 V24.78 V (10.33%)3252.7 WDrop/Amp High
3 AWG26.67 mm²100 A11.91 V (4.96%)228.1 V19.65 V (8.19%)2579.5 WDrop/Amp High
2 AWG33.62 mm²115 A9.45 V (3.94%)230.5 V15.59 V (6.5%)2046.2 WDrop/Amp High
1 AWG42.41 mm²130 A7.49 V (3.12%)232.5 V12.36 V (5.15%)1622.1 W~ ≤5%
1/0 AWG53.49 mm²150 A5.94 V (2.48%)234.1 V9.8 V (4.08%)1286.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A4.71 V (1.96%)235.3 V7.77 V (3.24%)1020.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A3.74 V (1.56%)236.3 V6.17 V (2.57%)809.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.96 V (1.24%)237.0 V4.89 V (2.04%)641.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.51 V (1.04%)237.5 V4.14 V (1.72%)543.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.09 V (0.87%)237.9 V3.45 V (1.44%)452.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.79 V (0.75%)238.2 V2.96 V (1.23%)388.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.57 V (0.65%)238.4 V2.59 V (1.08%)339.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.25 V (0.52%)238.7 V2.07 V (0.86%)271.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.05 V (0.44%)239.0 V1.72 V (0.72%)226.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.84 V (0.35%)239.2 V1.38 V (0.57%)181.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.63 V (0.26%)239.4 V1.03 V (0.43%)135.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 225 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 225 feet one-way at 240V (3-Phase), you need 1/0 AWG copper wire. This produces a voltage drop of 5.94V (2.48%) and delivers 234.1V at the load.

What size aluminum wire is required for 125 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 6.17V (2.57%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.