🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 75 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 1.04%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 2.59V (1.08%)
Voltage at Load End237.5 VLoss: 2.5 V (540.7 W)
Power & Breaker (125%)51.96 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A50.92 V (21.22%)189.1 V84.0 V (35.0%)11024.7 WDrop/Amp High
12 AWG3.31 mm²20 A32.0 V (13.33%)208.0 V52.78 V (21.99%)6927.9 WDrop/Amp High
10 AWG5.26 mm²30 A20.14 V (8.39%)219.9 V33.22 V (13.84%)4359.6 WDrop/Amp High
8 AWG8.37 mm²50 A12.65 V (5.27%)227.3 V20.87 V (8.7%)2739.7 WDrop/Amp High
6 AWG13.3 mm²65 A7.96 V (3.32%)232.0 V13.14 V (5.47%)1724.2 WDrop/Amp High
4 AWG21.15 mm²85 A5.01 V (2.09%)235.0 V8.26 V (3.44%)1084.2 WDrop/Amp High
3 AWG26.67 mm²100 A3.97 V (1.65%)236.0 V6.55 V (2.73%)859.8 WDrop/Amp High
2 AWG33.62 mm²115 A3.15 V (1.31%)236.8 V5.2 V (2.17%)682.1 WDrop/Amp High
1 AWG42.41 mm²130 A2.5 V (1.04%)237.5 V4.12 V (1.72%)540.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.98 V (0.83%)238.0 V3.27 V (1.36%)428.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.57 V (0.65%)238.4 V2.59 V (1.08%)340.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.25 V (0.52%)238.8 V2.06 V (0.86%)269.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.99 V (0.41%)239.0 V1.63 V (0.68%)213.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.84 V (0.35%)239.2 V1.38 V (0.57%)181.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.7 V (0.29%)239.3 V1.15 V (0.48%)150.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.6 V (0.25%)239.4 V0.99 V (0.41%)129.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.52 V (0.22%)239.5 V0.86 V (0.36%)113.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.42 V (0.17%)239.6 V0.69 V (0.29%)90.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.35 V (0.15%)239.7 V0.57 V (0.24%)75.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.28 V (0.12%)239.7 V0.46 V (0.19%)60.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.21 V (0.09%)239.8 V0.34 V (0.14%)45.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 75 feet one-way at 240V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 2.5V (1.04%) and delivers 237.5V at the load.

What size aluminum wire is required for 125 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 2.59V (1.08%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.