🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

15 Amp Wire Size at 225 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.9%
Aluminum Wire (≤3% Drop)6 AWGDrop: 4.73V (1.97%)
Voltage at Load End235.4 VLoss: 4.56 V (118.4 W)
Power & Breaker (125%)6.24 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 225 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A18.33 V (7.64%)221.7 V30.24 V (12.6%)476.3 WDrop/Amp High
12 AWG3.31 mm²20 A11.52 V (4.8%)228.5 V19.0 V (7.92%)299.3 W~ ≤5%
10 AWG5.26 mm²30 A7.25 V (3.02%)232.8 V11.96 V (4.98%)188.3 W~ ≤5%
8 AWG8.37 mm²50 A4.56 V (1.9%)235.4 V7.51 V (3.13%)118.4 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.87 V (1.19%)237.1 V4.73 V (1.97%)74.5 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.8 V (0.75%)238.2 V2.97 V (1.24%)46.8 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.43 V (0.6%)238.6 V2.36 V (0.98%)37.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.13 V (0.47%)238.9 V1.87 V (0.78%)29.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.9 V (0.37%)239.1 V1.48 V (0.62%)23.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.71 V (0.3%)239.3 V1.18 V (0.49%)18.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.57 V (0.24%)239.4 V0.93 V (0.39%)14.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.45 V (0.19%)239.6 V0.74 V (0.31%)11.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.36 V (0.15%)239.6 V0.59 V (0.24%)9.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.3 V (0.13%)239.7 V0.5 V (0.21%)7.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.25 V (0.1%)239.7 V0.41 V (0.17%)6.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.22 V (0.09%)239.8 V0.35 V (0.15%)5.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.19 V (0.08%)239.8 V0.31 V (0.13%)4.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.15 V (0.06%)239.8 V0.25 V (0.1%)3.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.13 V (0.05%)239.9 V0.21 V (0.09%)3.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.1 V (0.04%)239.9 V0.17 V (0.07%)2.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.03%)239.9 V0.12 V (0.05%)2.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 225 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 225 feet one-way at 240V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 4.56V (1.9%) and delivers 235.4V at the load.

What size aluminum wire is required for 15 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 4.73V (1.97%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.