⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 250 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.52%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 6.27V (2.61%)
Voltage at Load End234.0 VLoss: 6.05 V (755.7 W)
Power & Breaker (125%)30.0 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 250 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A196.0 V (81.66%)44.0 V323.3 V (134.71%)24499.4 WDrop/Amp High
12 AWG3.31 mm²20 A123.16 V (51.32%)116.8 V203.16 V (84.65%)15395.4 WDrop/Amp High
10 AWG5.26 mm²30 A77.5 V (32.29%)162.5 V127.85 V (53.27%)9688.0 WDrop/Amp High
8 AWG8.37 mm²50 A48.71 V (20.29%)191.3 V80.34 V (33.48%)6088.3 WDrop/Amp High
6 AWG13.3 mm²65 A30.65 V (12.77%)209.3 V50.56 V (21.07%)3831.5 WDrop/Amp High
4 AWG21.15 mm²85 A19.28 V (8.03%)220.7 V31.8 V (13.25%)2409.4 WDrop/Amp High
3 AWG26.67 mm²100 A15.29 V (6.37%)224.7 V25.21 V (10.51%)1910.7 WDrop/Amp High
2 AWG33.62 mm²115 A12.13 V (5.05%)227.9 V20.0 V (8.33%)1515.7 WDrop/Amp High
1 AWG42.41 mm²130 A9.61 V (4.01%)230.4 V15.86 V (6.61%)1201.6 W~ ≤5%
1/0 AWG53.49 mm²150 A7.62 V (3.18%)232.4 V12.57 V (5.24%)952.7 W~ ≤5%
2/0 AWG67.43 mm²175 A6.05 V (2.52%)234.0 V9.97 V (4.16%)755.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.8 V (2.0%)235.2 V7.91 V (3.3%)599.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.8 V (1.58%)236.2 V6.27 V (2.61%)475.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.22 V (1.34%)236.8 V5.31 V (2.21%)402.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.68 V (1.12%)237.3 V4.42 V (1.84%)335.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.3 V (0.96%)237.7 V3.79 V (1.58%)287.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.01 V (0.84%)238.0 V3.32 V (1.38%)251.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.61 V (0.67%)238.4 V2.65 V (1.11%)201.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.34 V (0.56%)238.7 V2.21 V (0.92%)167.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.07 V (0.45%)238.9 V1.77 V (0.74%)134.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.8 V (0.34%)239.2 V1.33 V (0.55%)100.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 250 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 250 feet one-way at 240V (1-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 6.05V (2.52%) and delivers 234.0V at the load.

What size aluminum wire is required for 125 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 6.27V (2.61%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.