⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 175 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.8%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 6.98V (2.91%)
Voltage at Load End233.3 VLoss: 6.73 V (841.1 W)
Power & Breaker (125%)30.0 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A137.2 V (57.17%)102.8 V226.31 V (94.3%)17149.6 WDrop/Amp High
12 AWG3.31 mm²20 A86.21 V (35.92%)153.8 V142.21 V (59.26%)10776.8 WDrop/Amp High
10 AWG5.26 mm²30 A54.25 V (22.61%)185.7 V89.49 V (37.29%)6781.6 WDrop/Amp High
8 AWG8.37 mm²50 A34.09 V (14.21%)205.9 V56.24 V (23.43%)4261.8 WDrop/Amp High
6 AWG13.3 mm²65 A21.46 V (8.94%)218.5 V35.39 V (14.75%)2682.0 WDrop/Amp High
4 AWG21.15 mm²85 A13.49 V (5.62%)226.5 V22.26 V (9.27%)1686.6 WDrop/Amp High
3 AWG26.67 mm²100 A10.7 V (4.46%)229.3 V17.65 V (7.35%)1337.5 WDrop/Amp High
2 AWG33.62 mm²115 A8.49 V (3.54%)231.5 V14.0 V (5.83%)1061.0 WDrop/Amp High
1 AWG42.41 mm²130 A6.73 V (2.8%)233.3 V11.1 V (4.62%)841.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A5.33 V (2.22%)234.7 V8.8 V (3.67%)666.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A4.23 V (1.76%)235.8 V6.98 V (2.91%)529.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A3.36 V (1.4%)236.6 V5.54 V (2.31%)419.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.66 V (1.11%)237.3 V4.39 V (1.83%)332.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.25 V (0.94%)237.7 V3.72 V (1.55%)281.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.88 V (0.78%)238.1 V3.1 V (1.29%)234.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.61 V (0.67%)238.4 V2.65 V (1.11%)201.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.41 V (0.59%)238.6 V2.32 V (0.97%)176.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.13 V (0.47%)238.9 V1.86 V (0.77%)140.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.94 V (0.39%)239.1 V1.55 V (0.65%)117.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.75 V (0.31%)239.2 V1.24 V (0.52%)93.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.56 V (0.23%)239.4 V0.93 V (0.39%)70.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 175 feet one-way at 240V (1-Phase), you need 1 AWG copper wire. This produces a voltage drop of 6.73V (2.8%) and delivers 233.3V at the load.

What size aluminum wire is required for 125 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 6.98V (2.91%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.