🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 125 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.0%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 4.99V (2.08%)
Voltage at Load End235.2 VLoss: 4.81 V (600.8 W)
Power & Breaker (125%)30.0 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 125 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A98.0 V (40.83%)142.0 V161.65 V (67.35%)12249.7 WDrop/Amp High
12 AWG3.31 mm²20 A61.58 V (25.66%)178.4 V101.58 V (42.33%)7697.7 WDrop/Amp High
10 AWG5.26 mm²30 A38.75 V (16.15%)201.2 V63.92 V (26.63%)4844.0 WDrop/Amp High
8 AWG8.37 mm²50 A24.35 V (10.15%)215.6 V40.17 V (16.74%)3044.1 WDrop/Amp High
6 AWG13.3 mm²65 A15.33 V (6.39%)224.7 V25.28 V (10.53%)1915.7 WDrop/Amp High
4 AWG21.15 mm²85 A9.64 V (4.02%)230.4 V15.9 V (6.62%)1204.7 WDrop/Amp High
3 AWG26.67 mm²100 A7.64 V (3.18%)232.4 V12.61 V (5.25%)955.4 WDrop/Amp High
2 AWG33.62 mm²115 A6.06 V (2.53%)233.9 V10.0 V (4.17%)757.9 WDrop/Amp High
1 AWG42.41 mm²130 A4.81 V (2.0%)235.2 V7.93 V (3.3%)600.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A3.81 V (1.59%)236.2 V6.29 V (2.62%)476.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.02 V (1.26%)237.0 V4.99 V (2.08%)377.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.4 V (1.0%)237.6 V3.96 V (1.65%)299.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.9 V (0.79%)238.1 V3.14 V (1.31%)237.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.61 V (0.67%)238.4 V2.65 V (1.11%)201.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.34 V (0.56%)238.7 V2.21 V (0.92%)167.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.15 V (0.48%)238.9 V1.9 V (0.79%)143.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.01 V (0.42%)239.0 V1.66 V (0.69%)125.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.8 V (0.34%)239.2 V1.33 V (0.55%)100.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.67 V (0.28%)239.3 V1.11 V (0.46%)83.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.54 V (0.22%)239.5 V0.88 V (0.37%)67.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.4 V (0.17%)239.6 V0.66 V (0.28%)50.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 125 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 125 feet one-way at 240V (1-Phase), you need 1 AWG copper wire. This produces a voltage drop of 4.81V (2.0%) and delivers 235.2V at the load.

What size aluminum wire is required for 125 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 4.99V (2.08%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.