⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

400 Amp Wire Size at 250 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 400 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 1.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.25V (1.77%)
Voltage at Load End235.7 VLoss: 4.29 V (1716.5 W)
Power & Breaker (125%)96.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 400 Amps at 250 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A627.18 V (261.33%)0.0 V1034.56 V (431.07%)250873.8 WDrop/Amp High
12 AWG3.31 mm²20 A394.12 V (164.22%)0.0 V650.12 V (270.88%)157648.8 WDrop/Amp High
10 AWG5.26 mm²30 A248.01 V (103.34%)0.0 V409.1 V (170.46%)99204.9 WDrop/Amp High
8 AWG8.37 mm²50 A155.86 V (64.94%)84.1 V257.1 V (107.12%)62343.8 WDrop/Amp High
6 AWG13.3 mm²65 A98.09 V (40.87%)141.9 V161.8 V (67.42%)39234.4 WDrop/Amp High
4 AWG21.15 mm²85 A61.68 V (25.7%)178.3 V101.74 V (42.39%)24672.2 WDrop/Amp High
3 AWG26.67 mm²100 A48.91 V (20.38%)191.1 V80.69 V (33.62%)19565.7 WDrop/Amp High
2 AWG33.62 mm²115 A38.8 V (16.17%)201.2 V64.01 V (26.67%)15521.0 WDrop/Amp High
1 AWG42.41 mm²130 A30.76 V (12.82%)209.2 V50.74 V (21.14%)12304.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A24.39 V (10.16%)215.6 V40.23 V (16.76%)9755.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A19.35 V (8.06%)220.7 V31.91 V (13.3%)7738.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A15.35 V (6.39%)224.7 V25.31 V (10.55%)6138.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.17 V (5.07%)227.8 V20.07 V (8.36%)4867.7 WDrop/Amp High
250 kcmil126.7 mm²255 A10.3 V (4.29%)229.7 V16.98 V (7.08%)4118.5 WDrop/Amp High
300 kcmil152.0 mm²285 A8.58 V (3.58%)231.4 V14.16 V (5.9%)3433.0 WDrop/Amp High
350 kcmil177.3 mm²310 A7.36 V (3.07%)232.6 V12.14 V (5.06%)2943.1 WDrop/Amp High
400 kcmil202.7 mm²335 A6.44 V (2.68%)233.6 V10.62 V (4.42%)2574.3 WDrop/Amp High
500 kcmil253.4 mm²380 A5.15 V (2.15%)234.9 V8.49 V (3.54%)2059.3 WDrop/Amp High
600 kcmil304.0 mm²420 A4.29 V (1.79%)235.7 V7.08 V (2.95%)1716.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.43 V (1.43%)236.6 V5.66 V (2.36%)1373.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.57 V (1.07%)237.4 V4.25 V (1.77%)1029.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 400 amps at 250 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 400A load over 250 feet one-way at 240V (1-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 4.29V (1.79%) and delivers 235.7V at the load.

What size aluminum wire is required for 400 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.25V (1.77%).

What breaker size is needed for a 400A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (400A × 1.25 = 500.0A), which corresponds to a standard 500A circuit breaker.