⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 75 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.4V (3.32%)
Voltage at Load End11.7 VLoss: 0.32 V (40.2 W)
Power & Breaker (125%)1.5 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 75 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A58.8 V (489.99%)0.0 V96.99 V (808.25%)7349.8 WDrop/Amp High
12 AWG3.31 mm²20 A36.95 V (307.91%)0.0 V60.95 V (507.9%)4618.6 WDrop/Amp High
10 AWG5.26 mm²30 A23.25 V (193.76%)0.0 V38.35 V (319.61%)2906.4 WDrop/Amp High
8 AWG8.37 mm²50 A14.61 V (121.77%)0.0 V24.1 V (200.86%)1826.5 WDrop/Amp High
6 AWG13.3 mm²65 A9.2 V (76.63%)2.8 V15.17 V (126.4%)1149.4 WDrop/Amp High
4 AWG21.15 mm²85 A5.78 V (48.19%)6.2 V9.54 V (79.49%)722.8 WDrop/Amp High
3 AWG26.67 mm²100 A4.59 V (38.21%)7.4 V7.56 V (63.04%)573.2 WDrop/Amp High
2 AWG33.62 mm²115 A3.64 V (30.31%)8.4 V6.0 V (50.0%)454.7 WDrop/Amp High
1 AWG42.41 mm²130 A2.88 V (24.03%)9.1 V4.76 V (39.64%)360.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.29 V (19.05%)9.7 V3.77 V (31.43%)285.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.81 V (15.11%)10.2 V2.99 V (24.93%)226.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.44 V (11.99%)10.6 V2.37 V (19.78%)179.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.14 V (9.51%)10.9 V1.88 V (15.68%)142.6 WDrop/Amp High
250 kcmil126.7 mm²255 A0.97 V (8.04%)11.0 V1.59 V (13.27%)120.7 WDrop/Amp High
300 kcmil152.0 mm²285 A0.8 V (6.71%)11.2 V1.33 V (11.06%)100.6 WDrop/Amp High
350 kcmil177.3 mm²310 A0.69 V (5.75%)11.3 V1.14 V (9.48%)86.2 WDrop/Amp High
400 kcmil202.7 mm²335 A0.6 V (5.03%)11.4 V1.0 V (8.29%)75.4 WDrop/Amp High
500 kcmil253.4 mm²380 A0.48 V (4.02%)11.5 V0.8 V (6.63%)60.3 W~ ≤5%
600 kcmil304.0 mm²420 A0.4 V (3.35%)11.6 V0.66 V (5.53%)50.3 W~ ≤5%
750 kcmil380.0 mm²475 A0.32 V (2.68%)11.7 V0.53 V (4.42%)40.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.24 V (2.01%)11.8 V0.4 V (3.32%)30.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 75 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 75 feet one-way at 12V (DC), you need 750 kcmil copper wire. This produces a voltage drop of 0.32V (2.68%) and delivers 11.7V at the load.

What size aluminum wire is required for 125 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.4V (3.32%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.