🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 125 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.66V (5.53%)
Voltage at Load End11.8 VLoss: 0.2 V (25.1 W)
Power & Breaker (125%)1.5 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 125 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A98.0 V (816.65%)0.0 V161.65 V (1347.09%)12249.7 WDrop/Amp High
12 AWG3.31 mm²20 A61.58 V (513.18%)0.0 V101.58 V (846.51%)7697.7 WDrop/Amp High
10 AWG5.26 mm²30 A38.75 V (322.93%)0.0 V63.92 V (532.69%)4844.0 WDrop/Amp High
8 AWG8.37 mm²50 A24.35 V (202.94%)0.0 V40.17 V (334.76%)3044.1 WDrop/Amp High
6 AWG13.3 mm²65 A15.33 V (127.72%)0.0 V25.28 V (210.67%)1915.7 WDrop/Amp High
4 AWG21.15 mm²85 A9.64 V (80.31%)2.4 V15.9 V (132.48%)1204.7 WDrop/Amp High
3 AWG26.67 mm²100 A7.64 V (63.69%)4.4 V12.61 V (105.06%)955.4 WDrop/Amp High
2 AWG33.62 mm²115 A6.06 V (50.52%)5.9 V10.0 V (83.34%)757.9 WDrop/Amp High
1 AWG42.41 mm²130 A4.81 V (40.05%)7.2 V7.93 V (66.07%)600.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.81 V (31.76%)8.2 V6.29 V (52.38%)476.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.02 V (25.19%)9.0 V4.99 V (41.55%)377.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.4 V (19.98%)9.6 V3.96 V (32.96%)299.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.9 V (15.85%)10.1 V3.14 V (26.14%)237.7 WDrop/Amp High
250 kcmil126.7 mm²255 A1.61 V (13.41%)10.4 V2.65 V (22.11%)201.1 WDrop/Amp High
300 kcmil152.0 mm²285 A1.34 V (11.18%)10.7 V2.21 V (18.43%)167.6 WDrop/Amp High
350 kcmil177.3 mm²310 A1.15 V (9.58%)10.9 V1.9 V (15.8%)143.7 WDrop/Amp High
400 kcmil202.7 mm²335 A1.01 V (8.38%)11.0 V1.66 V (13.82%)125.7 WDrop/Amp High
500 kcmil253.4 mm²380 A0.8 V (6.7%)11.2 V1.33 V (11.06%)100.6 WDrop/Amp High
600 kcmil304.0 mm²420 A0.67 V (5.59%)11.3 V1.11 V (9.22%)83.8 WDrop/Amp High
750 kcmil380.0 mm²475 A0.54 V (4.47%)11.5 V0.88 V (7.37%)67.1 W~ ≤5%
1000 kcmil506.7 mm²545 A0.4 V (3.35%)11.6 V0.66 V (5.53%)50.3 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 125 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 125 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.2V (1.68%) and delivers 11.8V at the load.

What size aluminum wire is required for 125 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.66V (5.53%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.