15 Amp Wire Size at 225 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)12 AWG3.31 mm² · Drop: 2.4%
Aluminum Wire (≤3% Drop)10 AWGDrop: 11.96V (2.49%)
Voltage at Load End468.5 VLoss: 11.52 V (299.3 W)
Power & Breaker (125%)12.47 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 225 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A18.33 V (3.82%)461.7 V30.24 V (6.3%)476.3 W~ ≤5%
12 AWG3.31 mm²20 A11.52 V (2.4%)468.5 V19.0 V (3.96%)299.3 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A7.25 V (1.51%)472.8 V11.96 V (2.49%)188.3 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A4.56 V (0.95%)475.4 V7.51 V (1.57%)118.4 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.87 V (0.6%)477.1 V4.73 V (0.99%)74.5 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.8 V (0.38%)478.2 V2.97 V (0.62%)46.8 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.43 V (0.3%)478.6 V2.36 V (0.49%)37.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.13 V (0.24%)478.9 V1.87 V (0.39%)29.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.9 V (0.19%)479.1 V1.48 V (0.31%)23.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.71 V (0.15%)479.3 V1.18 V (0.24%)18.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.57 V (0.12%)479.4 V0.93 V (0.19%)14.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.45 V (0.09%)479.6 V0.74 V (0.15%)11.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.36 V (0.07%)479.6 V0.59 V (0.12%)9.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.3 V (0.06%)479.7 V0.5 V (0.1%)7.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.25 V (0.05%)479.7 V0.41 V (0.09%)6.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.22 V (0.04%)479.8 V0.35 V (0.07%)5.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.19 V (0.04%)479.8 V0.31 V (0.06%)4.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.15 V (0.03%)479.8 V0.25 V (0.05%)3.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.13 V (0.03%)479.9 V0.21 V (0.04%)3.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.1 V (0.02%)479.9 V0.17 V (0.03%)2.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.02%)479.9 V0.12 V (0.03%)2.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 225 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 225 feet one-way at 480V (3-Phase), you need 12 AWG copper wire. This produces a voltage drop of 11.52V (2.4%) and delivers 468.5V at the load.

What size aluminum wire is required for 15 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 10 AWG to maintain voltage drop at 11.96V (2.49%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.