⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

300 Amp Wire Size at 225 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 300 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 0.9%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 4.96V (1.03%)
Voltage at Load End475.7 VLoss: 4.3 V (2234.9 W)
Power & Breaker (125%)249.42 kW400A Breaker Recommended

All AWG & kcmil Wire Gauges for 300 Amps at 225 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A366.63 V (76.38%)113.4 V604.77 V (125.99%)190507.3 WDrop/Amp High
12 AWG3.31 mm²20 A230.39 V (48.0%)249.6 V380.04 V (79.17%)119714.6 WDrop/Amp High
10 AWG5.26 mm²30 A144.98 V (30.2%)335.0 V239.15 V (49.82%)75333.7 WDrop/Amp High
8 AWG8.37 mm²50 A91.11 V (18.98%)388.9 V150.29 V (31.31%)47342.3 WDrop/Amp High
6 AWG13.3 mm²65 A57.34 V (11.95%)422.7 V94.58 V (19.7%)29793.6 WDrop/Amp High
4 AWG21.15 mm²85 A36.06 V (7.51%)443.9 V59.48 V (12.39%)18735.5 WDrop/Amp High
3 AWG26.67 mm²100 A28.59 V (5.96%)451.4 V47.17 V (9.83%)14857.7 WDrop/Amp High
2 AWG33.62 mm²115 A22.68 V (4.73%)457.3 V37.42 V (7.79%)11786.3 WDrop/Amp High
1 AWG42.41 mm²130 A17.98 V (3.75%)462.0 V29.66 V (6.18%)9343.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A14.26 V (2.97%)465.7 V23.52 V (4.9%)7408.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.31 V (2.36%)468.7 V18.66 V (3.89%)5876.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.97 V (1.87%)471.0 V14.8 V (3.08%)4661.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.11 V (1.48%)472.9 V11.73 V (2.44%)3696.4 WDrop/Amp High
250 kcmil126.7 mm²255 A6.02 V (1.25%)474.0 V9.93 V (2.07%)3127.5 WDrop/Amp High
300 kcmil152.0 mm²285 A5.02 V (1.05%)475.0 V8.28 V (1.72%)2606.9 WDrop/Amp High
350 kcmil177.3 mm²310 A4.3 V (0.9%)475.7 V7.09 V (1.48%)2234.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.76 V (0.78%)476.2 V6.21 V (1.29%)1954.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.01 V (0.63%)477.0 V4.96 V (1.03%)1563.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.51 V (0.52%)477.5 V4.14 V (0.86%)1303.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.01 V (0.42%)478.0 V3.31 V (0.69%)1042.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.51 V (0.31%)478.5 V2.48 V (0.52%)782.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 300 amps at 225 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 300A load over 225 feet one-way at 480V (3-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 4.3V (0.9%) and delivers 475.7V at the load.

What size aluminum wire is required for 300 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 4.96V (1.03%).

What breaker size is needed for a 300A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (300A × 1.25 = 375.0A), which corresponds to a standard 400A circuit breaker.