⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

15 Amp Wire Size at 125 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)14 AWG2.08 mm² · Drop: 2.12%
Aluminum Wire (≤3% Drop)12 AWGDrop: 10.56V (2.2%)
Voltage at Load End469.8 VLoss: 10.18 V (264.6 W)
Power & Breaker (125%)12.47 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 125 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A10.18 V (2.12%)469.8 V16.8 V (3.5%)264.6 W✓ PASS (≤3%)
12 AWG3.31 mm²20 A6.4 V (1.33%)473.6 V10.56 V (2.2%)166.3 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A4.03 V (0.84%)476.0 V6.64 V (1.38%)104.6 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A2.53 V (0.53%)477.5 V4.17 V (0.87%)65.8 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.59 V (0.33%)478.4 V2.63 V (0.55%)41.4 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.0 V (0.21%)479.0 V1.65 V (0.34%)26.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.79 V (0.17%)479.2 V1.31 V (0.27%)20.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.63 V (0.13%)479.4 V1.04 V (0.22%)16.4 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.5 V (0.1%)479.5 V0.82 V (0.17%)13.0 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.4 V (0.08%)479.6 V0.65 V (0.14%)10.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.31 V (0.07%)479.7 V0.52 V (0.11%)8.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.25 V (0.05%)479.8 V0.41 V (0.09%)6.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.2 V (0.04%)479.8 V0.33 V (0.07%)5.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.17 V (0.03%)479.8 V0.28 V (0.06%)4.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.14 V (0.03%)479.9 V0.23 V (0.05%)3.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.12 V (0.02%)479.9 V0.2 V (0.04%)3.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.1 V (0.02%)479.9 V0.17 V (0.04%)2.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.08 V (0.02%)479.9 V0.14 V (0.03%)2.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.07 V (0.01%)479.9 V0.11 V (0.02%)1.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.06 V (0.01%)479.9 V0.09 V (0.02%)1.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.04 V (0.01%)480.0 V0.07 V (0.01%)1.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 125 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 125 feet one-way at 480V (3-Phase), you need 14 AWG copper wire. This produces a voltage drop of 10.18V (2.12%) and delivers 469.8V at the load.

What size aluminum wire is required for 15 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 12 AWG to maintain voltage drop at 10.56V (2.2%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.