🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

30 Amp Wire Size at 30 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 30 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 2.91%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 0.29V (2.39%)
Voltage at Load End11.7 VLoss: 0.35 V (10.5 W)
Power & Breaker (125%)0.36 kW40A Breaker Recommended

All AWG & kcmil Wire Gauges for 30 Amps at 30 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A5.64 V (47.04%)6.4 V9.31 V (77.59%)169.3 WDrop/Amp High
12 AWG3.31 mm²20 A3.55 V (29.56%)8.5 V5.85 V (48.76%)106.4 WDrop/Amp High
10 AWG5.26 mm²30 A2.23 V (18.6%)9.8 V3.68 V (30.68%)67.0 WDrop/Amp High
8 AWG8.37 mm²50 A1.4 V (11.69%)10.6 V2.31 V (19.28%)42.1 WDrop/Amp High
6 AWG13.3 mm²65 A0.88 V (7.36%)11.1 V1.46 V (12.13%)26.5 WDrop/Amp High
4 AWG21.15 mm²85 A0.56 V (4.63%)11.4 V0.92 V (7.63%)16.7 W~ ≤5%
3 AWG26.67 mm²100 A0.44 V (3.67%)11.6 V0.73 V (6.05%)13.2 W~ ≤5%
2 AWG33.62 mm²115 A0.35 V (2.91%)11.7 V0.58 V (4.8%)10.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.28 V (2.31%)11.7 V0.46 V (3.81%)8.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.22 V (1.83%)11.8 V0.36 V (3.02%)6.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.17 V (1.45%)11.8 V0.29 V (2.39%)5.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.14 V (1.15%)11.9 V0.23 V (1.9%)4.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.11 V (0.91%)11.9 V0.18 V (1.51%)3.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.09 V (0.77%)11.9 V0.15 V (1.27%)2.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.08 V (0.64%)11.9 V0.13 V (1.06%)2.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.07 V (0.55%)11.9 V0.11 V (0.91%)2.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.06 V (0.48%)11.9 V0.1 V (0.8%)1.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.05 V (0.39%)12.0 V0.08 V (0.64%)1.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.04 V (0.32%)12.0 V0.06 V (0.53%)1.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.03 V (0.26%)12.0 V0.05 V (0.42%)0.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.02 V (0.19%)12.0 V0.04 V (0.32%)0.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 30 amps at 30 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 30A load over 30 feet one-way at 12V (DC), you need 2 AWG copper wire. This produces a voltage drop of 0.35V (2.91%) and delivers 11.7V at the load.

What size aluminum wire is required for 30 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 0.29V (2.39%).

What breaker size is needed for a 30A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (30A × 1.25 = 37.5A), which corresponds to a standard 40A circuit breaker.